Comat SMS Relay Manual de usuario

Comat SMS Relay
Operating Instructions
Tel +49 (0)7082-94 00 00
Kühn Controls AG, Gräfenhäuser Str. 14, D-75305 Neuenbürg, Germany
www kuehn-controls.de sales@kuehn-controls.de Fax +49 (0)7082-94 00 01
ba_smsrelay_0706e doc

2
Comat SMS Relay
Content
1 SMS Relay Operating Instructions 3
1 1 Short description of the CMS Comat Message System SMS Relay 3
1 2 Short instructions 3
1 3 Application examples 4
2 Safety instructions 4
3 Installation details/ scope of supply 5
4 Software 6
4 1 System requirements 6
4 2 Installation 7
5 Run Mode 8
5 1 LED status display 8
5 1 1 GSM-LED 8
5 1 2 Status-LED 8
5 1 3 Inputs / Outputs 8
5 2 Power failure 9
5 3 Diagnose 9
6 Configuration of the SMS Relay with the „FAST SMS Set“ ™ Software 9
6 1 General 9
6 2 Create connection 9
6 3 Edit Telephone book 10
6 4 Settings 10
6 4 1 Automatic provider search 11
6 4 2 Manual provider search 11
6 5 Status messages 12
6 6 Input configuration 12
6 6 1 General 12
6 6 2 Parallel message handling 13
6 6 3 Delayed switching on 14
6 6 4 Delayed switching off 14
6 7 Output configuration 15
6 7 1 General 15
6 7 2 Timer function 15
7 Language selection 16
7 1 General 16
7 2 Change / expand language library 16
8 Technical items 17
8 1 Dimension 17
8 2 Technical datas 17
Operating instructions SMS Relay ba_smsrelay_0706e doc

3
Comat SMS Relay
1. SMS Relay Operating Instructions
1.1 Short description of the CMS Comat Message System SMS Relay
The Comat CMS-10 SMS relay is a remote control and messaging system Six digital inputs
and four relay outputs with alternating contacts are monitored by means of a SMS (Short
Message System) via a mobile telephone network* (SIM card determines the provider) The
device’s own phone book saves up to 50 mobile phone numbers of the receivers Each
status change at the input sends a pre-defined message by SMS to the selected receivers
The receivers are processed cyclically, according to the order chosen The outputs can be
switched on and off by means of a pre-defined message by SMS In order to obtain an
overview of the state of the installation, the input and output status can also be queried by
SMS The relay outputs have a „time function“ The outputs are only switched on during the
preset time Unauthorised access can be controlled by activation of a password The SMS
relay sends out a message at regular intervals The same thing happens if there is a power
loss, whereby the SMS relay sends out a last message If the power is restored, the CMS 10
sends back a further message All these options can of course be switched on and off if
required The programming of the SMS Relay is carried out with the „FAST SMS Set“ tm
programming software that is provided In this way the settings can be configured
conveniently and easily
*GSM net ork: 850MHz, 900MHz, 1800MHz, 1900MHz (quad-band GSM module inside)
1.2 Short instructions
1 Switch off the SMS Relay
2 Place the SIM card in the card holder
3 Connect the RS232 interface of your PC or Notebook with the programming
interface of the SMS Relay Use the programming cable
4 Now switch on the SMS Relay
5 As soon as the SMS Relay is ready (after about 100 sec), start the programming
software FAST SMS Set
(Status-LED and GSM-LED are blinking regularly)
6 Choose your prepared file or create a new file with your configuration Please set
the correct PIN code
7 Select a free COM port (Menu Configuration – Select port)
8 Download the file to the SMS Relay ( download)
9 Wait until the SMS Relay is ready again (after about 100 sec)
10 Set the time and the date (Menu Configuration – Set time/date)
Operating instructions SMS Relay ba_smsrelay_0706e doc

4
Comat SMS Relay
1.3 Application examples
Heating control
Pump control
Irrigation installations
Alarm transmission
Level monitoring
Temperature monitoring
Pressure monitoring
Valve control
Voltage monitoring
2. Safety instructions
The electrical installation of the SMS relay must be carried out by a competent person
Please read the complete operating instructions before installation and commissioning
This device is not suitable for monitoring sensitive installations or time critical processes
GSM network failure or power interruptions cannot guarantee a secure monitoring The use
of a prepaid SIM card is possible It is recommended to use a SIM card with subscription
This avoids possible credit balance problems
The individual responsibility for protecting the SIM card against abuse lies solely with the
card owner
Comat AG does not accept any liability for possible damage to persons, buildings and/or
machines, which occur due to incorrect use or from not following the details Comat AG does
not accept any responsibility for the application and use of the SMS relay In particular
Comat AG cannot guarantee the connection security with the mobile network
Operating instructions SMS Relay ba_smsrelay_0706e doc

5
Comat SMS Relay
3. Installation details/ scope of supply
The SMS Relay comes together with the CMS-ANT small device antenna The place of
installation must be taken into account for the antenna selection
PLEASE NOTE:
The CMS-ANT small device antenna is not suitable for
installation in a s itch cabinet (shielding).
Here the CMS-ANT-MAG/2 5M antenna with magnetic feet or the CMS-ANT-SPEZ/5M
external signal antenna provide a much better result Please take this into account when
ordering Our product specialists will be glad to answer any questions
CMS-ANT CMS-ANT-MAG/2.5M CMS-ANT-SPEZ/5M
When connecting to the 230VAC mains it is absolutely necessary to ensure that the power
supply and the inputs power supply originate from the same phase i e a voltage above
240VAC must not arise on the device The SMS relay must be connected according to the
following schematic:
Connection CMS-10/AC110-240V Connection CMS-10/DC12-48V
The regulations and common standards are to be followed for the electrical installation and
the installation must be carried out by a competent person
Operating instructions SMS Relay ba_smsrelay_0706e doc

6
Comat SMS Relay
4. Soft are
4.1 System requirements
The „FAST SMS Set“ tm configuration software runs on the current Microsoft operating
systems The following minimum system requirements must be met in order that the software
functions properly:
Operating system:
Windows98
WindowsNT
WindowsME
Windows2000
WindowsXP
CPU computer capacity:
486er / 100MHz
Recommended: Pentium I / 400MHz
RAM:
256MB (WindowsXP)
Hard disc storage capacity available
40MB
Programming interface:
RS232
USB (with USB-RS232- interface converter e g CMS-USB)
*Screen resolution
minimal: 1024 x 768 pixels
*PLEASE NOTE:
If the screen resolution is too low, the window of the rogramming software
won’t be dis layed in his normal size. That means some tabs or buttons will
be invisible. To avoid this, change the screen resolution of your com uter
system. Select “Start” – “System controls” – “Dis lay” and then the register
“Settings”. Please set the screen resolution to 1024 x 768 ixels in minimum.
Operating instructions SMS Relay ba_smsrelay_0706e doc

7
Comat SMS Relay
4.2 Installation
Once the CD-ROM is inserted, the installation menu starts automatically, if this is not the
case then the CD-ROM can be started by double clicking „Start“ in the WindowsExplorer
The installation menu is available in different languages Please choose the required
language You can install the software on your computer or start it directly from the CD-ROM
without installing Please follow the set-up programme instructions during installation
The SMS relay starts up automatically once power has been supplied When the signal is
strong enough the device will register itself in the GSM network (according to the SIM card
settings, depending on provider) Both LEDs will display the actual device and network
status
Operating instructions SMS Relay ba_smsrelay_0706e doc

8
Comat SMS Relay
5. Run Mode
5.1 LED status display
The SMS relay has two LEDs, the GSM LED und the status LED Both LEDs can be seen
from the outside and are located below the cover The following states are displayed:
5.1.1 GSM-LED
- flashing regularly (every second) Module is not registered in the GSM
network
- short flashing (approx every three seconds) Module is registered but there is no
communication
- Continuous lighting Communication connection is made
- Irregular flashing Data are transmitted (SMS)
5.1.2 Status-LED
- dark LED Device does not run
- intermittent flashing (irregular) Device starts up
- short flashing (like GSM LED, approx every 3s) 1x Device runs, everything OK
- short flashing (like GSM LED, approx every 3s) 2x no credit left
- short flashing (like GSM LED, approx every 3s) 3x Clock not adjusted
- flashing regularly (every second) 1x Module in initial state
- flashing regularly (every second) 2x configuration error
- flashing regularly (every second) 3x communication error
5.1.3 Inputs / Outputs
In addition the states of the inputs and outputs are displayed by means of an LED These
LEDs are designated as follows:
Inputs I1, I2, I3, I4, I5, I6 (LED lighting = input is switched on)
Outputs Q1, Q2, Q3, Q4 (LED lighting = output is switched on)
LED positions of the SMS Relay
Operating instructions SMS Relay ba_smsrelay_0706e doc
Status-LED
Inputs
Outputs
GSM-LED

9
Comat SMS Relay
5.2 Po er failure
Short power failures (t < 1s) are tolerated by the power supply and do not change the module
status
Longer power failures (t ≥ 1s) are registered and can trigger an SMS alarm message
depending on the adjustment Afterwards the device shuts down After restarting the device
the states of the outputs and the registration of the SMS Relay in the GSM network are
restored to the same status as before the voltage failure (Memory function)
5.3 Diagnose
The SMS Relay together with the programming software „FAST SMS Set™“ allow to display
the actual signal quality For that function the SMS Relay has to be connected with a PC /
laptop via the programming cable To get to the diagnose select “Configuration – Diagnose”
from the menu in the programming software In addition to the signal quality the diagnose will
display some more information like different version numbers of the device and the firmware
6 Configuration of the SMS Relay ith the „FAST SMS Set“ ™ Soft are
6.1 General
The SMS Relay is configured and prepared fro use with the „FAST SMS Set™“ software The
SMS Relay can be prepared before installation i e the SMS Relay configuration (telephone
book creation, input messages) can be created without connecting to the device In order to
do this the software is started, a new or existing file opened and edited The file created
needs only to be downloaded to the SMS Relay with the CMS-RS232 programming cable In
offline mode the diagnostics are not active The diagnostics can only be accessed once the
SMS Relay is connected by the RS232 serial interface to the PC
6.2 Create connection
•Switch off the SMS Relay
•Insert the SIM card
•Connect the RS232 interface of your PC or Notebook with the SMS Relay programming
interface using the CMS-RS232 programming cable If your PC or Notebook does not
have an RS232 interface then use a CMS-USB interface converter. With this you can
directly connect the rogramming cable to one of your USB in uts.
•Switch on the SMS Relay
•As soon as the Status-LED of the SMS Relay lights permanently, you can start the
software
•Choose the required file or create a new one
•For transmission, choose the required COM port on your PC This is carried out in the
„Configuration – Select port“ menu
Now you are ready to configure the SMS Relay according to your needs or to download the
prepared files
Operating instructions SMS Relay ba_smsrelay_0706e doc

10
Comat SMS Relay
6.3 Edit Telephone book
The software offers the possibility to manage up to 50 telephone numbers
New – capture of a new phone number
Editing – editing of an already existing and labelled phone number
Deleting – deleting of an existing and labelled phone number
Checking – checks whether the labelled entry is already captured in the telephone book
Please enter the phone number in international format (i e with country code and prefix) ,
e g +41793333333 (+41 Switzerland; +49 Germany, +31 Holland, etc)
In the„Name“ data field the list can be sorted in ascending or descending alphabetical order
The sorting does not influence entries which have already been used
SMS Relay Phonebook editor
6.4 Settings
You can now configure the SMS Relay according to your application The default settings for
SMS transmission contain important general data which help identify the device The SIM
card can be protected with PIN code just like for normal mobile phone operation The PIN
request is activated and the PIN code is inputted in the required field This concerns PIN1
Further information can be obtained from the SIM card leaflet Likewise the process of
unblocking the SIM card after three incorrect inputs of PIN1 is described In order to do this
the SIM card must be removed from the SMS Relay and inserted into a mobile phone Now
the card can be unblocked according to the network providers details
Operating instructions SMS Relay ba_smsrelay_0706e doc
Otros manuales para SMS Relay
1
Tabla de contenidos
Otros manuales de Mando a distancia de Comat