Page 10
GENIE C & S - SETUP & SERVICE MODES
Service Mode
This is a special mode used to set the operation of the Control and to investigate fault conditions, it is entered from User
Setup Mode.
Rotate Pool Thermostat knob fully clockwise to show the software version number.
Press the Lock/Reset Button for 3 seconds. The control is now in Service Mode.
It is now possible to change some of the Control’s parameters. To show them, rotate the Pool Thermostat
Potentiometer. To zero or change them, press the Reset/Lock button
To exit, turn the Panel Switch off then back on again.
Test Temperature Display Mode 1 (td1).
Temperatures are displayed to 0.1 degree resolution, not the normal 1 degree.
The display will now show each sensor temperature and cycle around them for each press of the Lock/Reset button.
1. Pool temperature as normally displayed. The green LED will be alight.
2. Pool temperature is dispayed to 0.1 degrees. The green LED will be alight.
3. Heat exchanger flow temperature. The yellow LED will flash rapidly.
4. Heat exchanger combustion temperature. The red LED will flash rapidly.
5. Aproximate pool water flow in l/m for Genie 50 multiply by 0.738 for Genie 35. the red and yellow LEDs
alternate.
Rotating the potentiometer will change the set temperature. Pressing and holding the button whilst one of the tem-
peratures is displayed will ‘lock/unlock’ it on the display for continuous observation.
Service Mode Setting Factory Setting Reset press Display Indicator
1 Pressure Log Number of Operations Resets to zero Yellow LED ON
2 Overheat Log Number of Operations Resets to zero Red LED ON
3 Combustion Gas Log Number of Operations Resets to zero Count, Red LED flashing
4 Gas Lockout Log Number of Operations Resets to zero Count, Red & Yellow LED ON
5 Condensate Blocked Log Number of Operations Resets to zero Count, Front Red PCB LED ON
6 Unused Rear Red PCB LED ON
7 Hours run 0 Press resets to zero 156 =1560 hrs both PCB LEDs on
8 Pool Temperature Offset 0.5 C (0.9 F) Steps of 0.5C (0.9F) -3.0C to 3.0C (-5.4 F to 5.4F)
9 Display td0 td1 td0 / td1
Genie S only
Genie C only
User Setup Mode Setting Factory Setting Alternative Display Indicator
1 Display units ° F = Fahrenheit ° C = Centigrade ° F or ° C
2 Maximum temperature 32 °C (90 °F) 41 °C ( 106 °F) PL or SPA
3 Software Version e.g 018