Ceil Static UPS System Manual de usuario


Dear Customer
We congratulate you for intelligently choosing CEIL Static UPS that incorporates latest DSP
controlled IGBT base technology.
This manual pro ides you a thorough understanding of your Static UPS and its optimum use.
Please read the installation and operating instructions in this manual carefully before installing
and using your CEIL Static UPS. Pay special attention to the section under PRECAUTIONS. Here
the manual pinpoints conditions or practices which could not only result in damage to your
Static UPS or other equipment but also result in personal injury or loss of life.
Should you need help at any time please feel free to contact us, we would welcome any
queries/suggestions from you that will enable us to impro e product quality and also offer you
better ser ice.
With best wishes and warm regards
Management Team
Exide Industries Limited India.
Important Safety Instructions
• Read this manual thoroughly before operation.
• Keep this instruction booklet safe.
• This unit is intended for installation in a temperature controlled, indoor area free from
conducti e contaminates.
• Make sure your AC input is properly grounded. Improper grounding might cause hazard
and is against WARRANTY condition.
• While cleaning, do not apply any chemical sol ent to the unit. Use dry cloth to a oid
anything dripping into the circuit.
• Keep the unit away from damp areas.
• Do not lea e the unit in direct sunlight.

Contents
Topic Page no.
Knowing your CEIL DSP Sine wa e Static UPS 1
Front Panel 1
Back Panel 2
Display Status 3
Some Safety Measures 4
Concept of Charging 6
Getting Started 7
Installing your Static UPS 8
Operation
Installation Diagram 10
Technical Specifications 11
Troubleshooting 12
Test Report of Static UPS 13
Installation Check List 14

Knowing your Static UPS
A static UPS ensures uninterrupted power supply to large electrical loads of commercial and
residential establishments during power outage. In its most basic form, a Static UPS transforms
Alternating Current (AC) to Direct Current (DC) for pro iding the required charging current for
the Battery Bank connected with it and also, to con ert Direct Current (DC) of the Battery Bank
to Alternating Current (AC) for the electrical loads. The Battery Bank with the Static UPS acts as
a reser oir to ensure continuous supply of power whene er mains supply from utility power is
not a ailable.
Front Panel:
Front Panel Diagram
Position No. unction Remarks
1 LCD Display all parameter
2 ON/OFF ON/OFF Switch
Status: Battery Voltage, Output Voltage, battery Charging and charged, Output Load in Static
In erter Mode and Mains Voltage.

REAR Panel
Position
No.
unction Remarks
3 Fan For cooling the Unit
4 Inbuilt time Delay To run compressor load like A.C.Time delay relay
(TDR) has been pro ided.
5 AC Mains MCB To switch on the AC main (Utility Power)
6 Battery MCB To switch on the DC supply
7 AC Mains For AC mains connection
8 Output For output load connection
9 Battery Terminal
Negati e (Black)
To connect battery wire black
10 Battery Terminal Positi e
(Red)
To connect battery wire red
11 BYPASS switch In case of system failure to BYPASS the system
12 In erter/UPS To toggle the system in In erter or UPS mode

Display Status
Status On Display Alarm
IUPS I/P……………………..Volt No
running on mains O/P…………………… Volt
I/P Freq……………..Hz
O/P Freq…………… Hz
Battery Charging
Battery ………………Volt
Mains OK
Load……………………%
Battery Low Protection Battery Low Beeping
Output o er load Warning Beeping
O erload
I/P MCB Trip I/P MCB Trip Beeping
O/P Short Circuit Protection Short Circuit Beeping
UPS on Battery Mains not OK Beeping E ery 5 Min.
I/P……………………..Volt
O/P…………………… Volt
I/P Freq……………..Hz
O/P Freq…………… Hz
Load %
O er Temp. Protection O er Temp. Yes

SOME SA ETY MEASURES
Important Precautions:
CEIL DSP Sine wa e Static USP has two Battery terminals coming out from the rear side, an AC
MCB, a DC MCB, an AC output socket and an AC Input socket. Battery terminals are red and
black in colour. The red colour terminal has to be connected to the POSITIVE TERMINAL of the
battery and black one to the NEGATIVE TERMINAL.
CAUTION:
Do not reverse the battery connections as it will trip the Battery MCB/ use.
Ensure that the incoming phase (or line) is connected to 'L', Neutral is connected to 'N' and
earth is connected through OUTPUT socket of the Static UPS.
General Precautions:
Before using the CEIL DSP Sine wa e Static UPS read all instructions and caution
markings on the Static UPS, the batteries and all appropriate sections of this Instruction
manual.
Do not expose CEIL DSP Sine wa e Static UPS to any type of chemicals.
Do not disassemble the CEIL DSP Sine wa e Static UPS. Take it to a qualified our
Engineering Ser ice Centre when ser ice or repair is required. Opening by unqualified
person can lead to electrical shock or fire hazard.
To reduce risks of electric shock disconnect all wiring before cleaning.
WARNING:
A oid exposing the Static UPS or Batteries to any type of explosi e gases in the icinity as
batteries generate explosi e gases during normal operation. Ensure proper entilation for the
battery compartments. The Battery enclosures should be so designed as to pre ent
accumulation and concentration of hydrogen gas in 'pockets' at the top of the compartment.
Vent the battery compartment from the highest point. A sloped lid can also be used to direct
the flow to the ent opening location. To reduce the risk of battery explosion, strictly follow the
instructions of the battery supplier for any equipment you intend to use in the icinity of
batteries.
Use the correct tools to make AC/DC wiring connections.
Do not install this CEIL DSP Sine wa e Static UPS on or near flammable materials
(plywood, chemicals, gasoline etc)

CAUTION:
The CEIL DSP Sine wave Static UPS should be connected to grounded, permanent wiring
systems.
Personal Precautions:
A person should be within the range of your oice so as to come to your aid when you
work near batteries
Keep plenty of fresh water and soap nearby in the e ent that battery acid comes in
contact with skin, clothing or eyes.
A oid touching eyes while working near batteries; Wash your hands when work done.
If battery acid comes in contact with skin or clothing wash immediately with soap and
water. If acid enters eyes immediately flood eyes with running cool water for at least 15
minutes and get medical attention immediately.
Baking soda neutralizes battery electrolyte.
NEVER smoke or allow spark or a flame in the icinity of the battery.
Be extra cautious when working with metal tools on and around batteries. It could
short-circuit the batteries or other electrical parts, producing a spark that could cause
an explosion.
Remo e personal metal items such as rings, bracelets, necklace and watches when
working with the battery. Battery can produce short-circuit current high enough to
cause se ere burns.
Ne er attempt to charge a frozen battery.
Before touching the Battery terminal makes sure that the Static UPS front switch is OFF
and AC mains to the Static UPS is also OFF.
If it is necessary to remo e any battery, always remo e the grounded terminal from the
battery first. Make sure all the accessories are off, so as not to cause arcing.
Be sure that the area around the battery is well entilated.
Clean battery terminals. Be careful not to allow corrosion to come in contact with eyes.
Study specific precautions and recommended rates of charge of all battery
manufacturers.
Add only distilled water in each cell until battery acid reaches le el specified by battery
manufacturer. This helps purge excessi e gas from cells. Do not o erfill. For a battery
without caps, carefully follow manufacturer's recharging instructions.
Exide India, is not responsible for any kind of battery related problems.

CONCEPT O CHARGING
ive Stage Pulse Charging
Bulk:
Batteries are charged at maximum allowed continuous constant charging current at constant
oltage for speedy charging of battery up to 13.8V (for a 12V battery).
Boost:
The charger checks the charging current when the battery oltage reaches 13.6V for 12V
batteries. The boost mode of the charger will be acti ated, which will boost the battery up to
20% more than its rated oltage (14.4V for 12V batteries) and charging current is reduced to
50% of bulk charging rate (i.e. 4 to 5AMP).
Taper:
When the oltage le el of battery is 20% more than its rated oltage, the taper mode of the
charger will be acti ated, which will keep the charging current at about 4AMP to achie e the
specific gra ity of electrolyte for fully charged battery.
loat:
In float stage the charger keeps the charging oltage& current le el at its trickle charging set
point of 13.6 V with minimum charging current at 1.0 AMP.
Pulse (Reset):
To maintain the float le el, the charger resets to zero current at 13.6V for some time and starts
again with pulse charging of <1 AMP current at same oltage. This keeps the battery in full
charge condition e en when not in use.

GETTING STARTED
Environment
Static UPS / In erters are sophisticated de ices and must be treated accordingly. Keep the Static
UPS in a non-condensing, well- entilated en ironment, ensuring there is no ingress of moisture
or foreign material.
Location
Static UPS should be kept as close as possible to the battery in order to keep the battery cables
short. Howe er do not locate the Static UPS in the same compartment as non-sealed batteries
since the gas from battery generator gases is ery corrosi e and can damage electronic
equipment and other items.
Important Precaution
The output side of the Static UPS AC wiring should ne er be connected to a generator or
incoming utility power. This condition is far worse than a short circuit. If the unit sur i es this
condition, it will shut down until correction is made.
An independent circuit breaker (MCB/MCCB) is suggested for INPUT & OUTPUT according to
the CEIL Static UPS capacity.
or Input, Output, battery wire thickness refers to table below.
UPS (KVA)
I/P WIRE O/P WIRE BATTERY
THICKNESS THICKNESS WIRE
(sq. mm) (sq. mm)
THICKNESS
(sq. mm)
2.5 KVA-36/48 VOLT 2.5 2.5 10
3 KVA-36/48 VOLT 2.5 2.5 16
5 KVA-48/96/120/180 VOLT 6 6 10
7.5 KVA-120/180 VOLT 10 10 16
10 KVA-180/192 VOLT 10 10 10
12 KVA-192 VOLT 16 16 16
Tabla de contenidos
Manuales populares de Unión Postal Universal de otras marcas

Pylontech
Pylontech Victron & Pylontech US5000 Manual de usuario

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manual de usuario

Mecer
Mecer ME-1000-WTU Manual de usuario

Mustek
Mustek PowerMust 530(B) Plus Manual de instalación y operación

Emerson
Emerson Liebert NXL series Manual de usuario

MAKELSAN
MAKELSAN BOXER SERIES Manual de usuario