HEALTH AND SAFETY WARNING
As the dehumidifier embodies electrical and rotational equipment, ONLY competent
persons should carry out any work on this type of machine. (See warranty).
OWNER/INSTALLATION MANUAL
WALLHUNG/FLOORSTANDING
DEHUMIDIFIERS
DH44/66 RANGE
SD496250 ISS 2
Contents
1.1 MOUNTING, POSITION ....................................................................................................................... 2
1.2 WALL HANGING/FLOORSTANDING ..................................................................................................4
2.1 CONDENSATE DRAIN CONNECTION ................................................................................................ 5
2.2 ELECTRICAL CONNECTION .............................................................................................................. 6
3.0 HUMIDISTAT SETTINGS ..................................................................................................................... 7
4.1 OPTIONAL HUMIDISTAT/AIRSTAT ..................................................................................................... 8
4.2 OPTIONAL LPHW ............................................................................................................................. 10
4.3 OPTIONAL AIR FILTER ..................................................................................................................... 11
5.1 OPERATION ...................................................................................................................................... 12
5.2 SERVICE NOTES .............................................................................................................................. 12
6.0 TECHNICAL DATA ............................................................................................................................. 13
7.0 WIRING DIAGRAMS .......................................................................................................................... 14
8.0 WARRANTY CONDITIONS ............................................................................................................... 18
R
CALOREX HEAT PUMPS & DEHUMIDIFIERS
The Causeway, Maldon, Essex CM9 5PU
Service No: +44(0)1621 857171
Tel No: +44(0)1621 856611
Fax No: +44(0)1621 850871
Email: [email protected]
Website http://www.calorex.com


Page 2
200 MINIMUM 200 MINIMUM
200 MINIMUM
For optimum performance of the dehumidifier, care needs to be taken when considering it’s
position.
1. Good air circulation.
2. The unit needs to be horizontally level.
3. At least 200mm away from ceiling and corners of the room.
4. At least 200mm service access is required.
5. If the dehumidifier is positioned on a wall, the wall needs to be load bearing. (A plaster-
board or wood cladded wall is not sufficiently strong).
1.1 MOUNTING, POSITION

Page 3
2)THE ISOLATOR FOR THE DEHUMIDIFIER MUST COMPLY TO THE APPROPRIATE IPX REGULATION
CAN BE WITHIN 1,25M BUT
MUST THEN BE 2,5M ABOVE
POOL SURFACE
1) N.B. THE RCD IS AN EARTH LEAKAGE TRIP & ALTHOUGH NOT ALWAYS REQUIRED
IT IS RECOMMENDED THAT IT IS USED ON ALL INSTALLATIONS. (A 30mA RCD SHOULD BE USED).
IF THE UNIT IS WITHIN 1,25M
OF THE POOL HORIZONTALLY
THEN IT MUST BE 2,5M ABOVE
THE POOL SURFACE.
ALTHOUGH THE UNIT IS 2,5M
ABOVE THE HEIGHT OF THE
POOL IT IS NOT ACCESSIBLE
FOR SERVICE & SO BREAKS
THE NEW REGULATIONS
2,5M
1,25 - 2,0M MUST BE FITTED WITH AN RCD
AND BE AT LEAST 300mm FROM FLOOR
MUST BE FITTED WITH RCD
ANY HEIGHT ACCEPTABLE
2,0-3,5M
16TH EDITION REGULATIONS AND CALOREX UNITS

Page 4
1.2 WALL HANGING/FLOOR STANDING
1345.00
80.00
540.00
1080.00
80.00
80.00
622.00
931.00
CHECK BRACKET
IS LEVEL CHECK ALL
FIXINGS
ARE TIGHT
WALL BRACKET
MACHINE BRACKET
ANTIVIBRATION
BUFFER POSITIONS
WALL BRACKET
MACHINE BRACKET
ANTIVIBRATION
BUFFER
POSITIONS
CHECK
BRACKET
IS LEVEL CHECK ALL
FIXINGS
ARE TIGHT
80.00 80.00 80.00
880.00
622.00
315.00
630.00
931.00
WALL
REMOVE
GROMMETS
95.00
MAX
30.00
340.00
274.20
294.20
FIT
ANTIVIBRATION
BUFFERS
DH44 MODEL
DH66 MODEL
When the dehumidifier is unpacked it is suitable for use standing on the floor. The feet can be
adjusted to allow for unevenness in the surface. If the unit is to be mounted on a wall, the
complete package contains wall brackets and antivibration buffers. Once the unit has been
hung on the wall the floor stand arrangement can be removed. Access to the fixings for the
stand arrangement can be gained by removing the round grommets in the feet.

Page 5
DH66 DEHUMIDIFIER SHOWN.
POSITIONS OF KNOCKOUTS FOR CONDENSATE DRAIN CONNECTION
CONDENSATE
DRAIN
L
40.00
40.00
110.00
110.00
CONDENSATE
DRAIN
22.00
100.00
20%
80%
60%
40%
22.00
100.00
2.1 CONDENSATE DRAIN CONNECTION
The condensate output and electrical connections can be at either end of the machine, at the
side or in the back, depending on the requirements of the user. To gain access to the unit
remove the covers, unscrewing the fixing screw in both end mouldings.The driptray can be
removed and turned round. Remove the desired knockouts, insert grommet (supplied) and
route condensate pipe through the knockout.(Tube outside diameter 19mm).
REMOVAL OF COVERS

Page 6
2.2 ELECTRICAL CONNECTION
30.00
22.00
20%
80%
60%
40%
22.00
30.00
ELECTRICAL
ENTRY POINT
ELECTRICAL
ENTRY POINT
45.00
40.00
45.00
40.00
POSITION OF
ELECTRIC BOX
The electrical connection should be carried out by an authorised electrician, paying special
attention to the latest IEE regulations. In any case, the mains power supply should be fitted with
a 30mA/30ms protection switch. The cable access position can be selected by the customer
from the positions shown above. Once the desired knockout has been removed a cable gland
(supplied in package) can be fitted to neaten off the hole.
The electric box is situated under the compressor cover which will need to be removed.
The connections are made to the terminal box on the outside of the electric box in the bottom
right hand corner of the dehumidifier.
FAN MODE SWITCH
A fan mode switch is positioned on the electric box with the following modes:
Fan continuous - continuous operation of the fan.
Fan cycle - the fan will be switched on and off automatically by the humidistat.
The mode “fan cycle” helps, especially with a covered swimming pool, to save energy:
(but in this mode larger humidity swings may be experienced).
After connecting the electrical supply, the compressor cover and machine cover need to be
installed in the manner shown on page 5.
The dehumidifier is now ready to operate.
Attention. The dehumidifier should not be switched on without it’s covers in place. Operation
without a cover causes poor airflow. Due to safety features the unit will switch off after a short
period of time.
DH66 DEHUMIDIFIER SHOWN
POSITIONS OF KNOCKOUTS FOR ELECTRICAL CONNECTION

Page 7
60%
3.0 HUMIDISTAT SETTINGS
The dehumidifier is provided with automatic control by a humidistat that can be adjusted to suit
room requirements. Adjustment is by a dial that is located on the right hand side of the unit. The
dial is marked as % relative humidity. When the % relative humidity is lower, the air is drier.
To set the dial, turn it so that the requred room humidity is positioned adjacent to the reference
mark as shown below. A room relative humidity of 50% to 60% is recommended. To operate the
dehuidifier continuously or to test its operation, turn the dial to the 20% position. In this position
the fan and compressor will run continuously (after the initial 6 minute time delay).
REFERENCE MARKER ON SIDE MOULDING
(ENLARGED FOR CLARITY)
FOR OTHER
SETTINGS
SEE DIAL

Page 8
4.1 OPTIONAL HUMIDISTAT/AIRSTAT
WITH REMOTE HUMIDISTAT FITTED ENSURE HUMIDISTAT
IN MACHINE IS SET FULLY CLOCKWISE (IE MAXIMUM DEHUMIDIFICATION)
REMOVE PINK WIRE LINK
12V REMOTE HUMIDISTAT CONNECTIONS
1mm SQ CABLE
250M MAX
HUMIDISTAT
(NOT SUPPLIED, WE
RECOMMEND CALOREX
PART SD385250.
SIEBE PART No.119 1701
91100) REMOVE
LINK
BOILER DEMAND
SIGNAL VOLT FREE
HUMIDISTAT
N (L2)
L (L1)
E (GND)
8
7
6
5
4
3
2
1
AIR STAT
COMMON
12V REMOTE AIR THERMOSTAT CONNECTIONS
FOR M/C WITH RESISTANCE HEATERS OR LPHW
12V REMOTE AIR THERMOSTAT CONNECTIONS
1mm SQ CABLE
250M MAX
AIR STAT
(NOT SUPPLIED, WE
RECOMMEND CALOREX
PART SD385251.
INVENSIS TYPE RTR-E6705,
PART No.111 170951 100).
HUMIDISTAT
N (L2)
L (L1)
E (GND)
BOILER DEMAND
SIGNAL VOLT FREE
8
7
6
5
4
3
2
1
AIR STAT
COMMON

Page 9
WITH REMOTE HUMIDISTAT/AIR STAT FITTED ENSURE HUMIDISTAT
IN MACHINE IS SET FULLY CLOCKWISE (IE MAXIMUM DEHUMIDIFICATION)
REMOVE PINK WIRE LINK
12V COMBINED REMOTE HUMIDISTAT/AIR STAT CONNECTIONS
1mm SQ CABLE
250M MAX
HUMIDISTAT/AIR STAT
(NOT SUPPLIED, WE
RECOMMEND CALOREX PART
SD385252.
EBERLE PART No.HYG-E-7001)
REMOVE
LINK
BOILER DEMAND
SIGNAL VOLT FREE
HUMIDISTAT
N (L2)
L (L1)
E (GND)
8
7
6
5
4
3
2
1
AIR STAT
COMMON
5
2
7