Bender EDS440 Manual de instrucciones

ISOSCAN® EDS440 and EDS441
Insulation fault locator to locate insulation faults in
ungrounded DC, AC and three-phase power supplies
EDS44x_D0020 _ _D_XXEN/ .2023

ISOSCAN® EDS440 and EDS441 Insulation fault locator to locate insulation faults in
ungrounded DC AC and three-phase power supplies
System properties
•Universal system design
•Modular design, therefore easily
adjustable to the given circumstances
•Measuring current transformers
available in various sizes and versions
•CT connection monitoring
•Twelve measuring channels for series
W…, WR…, WS… measuring current
transformers
•Optional extension by twelve relay
channels
•Fault memory behaviour selectable
•Up to 50 EDS insulation fault locators in
the system, 600 measuring channels
•Response sensitivity:
– EDS440…: 2… 0 mA
– EDS44 …: 0.2… mA
•AC residual current measurement with
configurable response value
•Two alarm relays with one n/o contact
each
•n/o or n/c operation selectable
•External test/reset button
•Central display of faulty outgoing
circuits
•Serial interface RS-485, BS bus address
range 2…79
•Connection to higher-level control and
visualisation systems possible.
Intended use
The insulation fault locators ISOSCAN® EDS440 and EDS44 are used to locate insulation
faults in unearthed DC, AC and three-phase power supply systems (IT systems).
Depending on the locating current injector, AC and three-phase systems can be
monitored within the range from AC 42 to 000 V; DC systems, within the range from
DC 24 to 500 V.
An AC residual current can be indicated in these ranges:
•EDS440: 42… 000 Hz, 0. …20 A
•EDS44 : 42…60 Hz, 0. …2 A
An EDS system (insulation fault location system) consists of an EDS44x insulation
fault locator and a locating current injector. EDS44… insulation fault locators detect
locating current signals generated by the locating current injector via measuring current
transformers and evaluate them accordingly.
Intended use also implies
•the observation of all information in the operating manual and
•compliance with test intervals.
In order to meet the requirements of the applicable standards, customised parameter
settings must be made on the equipment in order to adapt it to local equipment and
operating conditions. Please heed the limits of the range of application indicated in the
technical data.
Do not make any unauthorised changes to the device. Only use spare parts and optional
accessories sold or recommended by the manufacturer.
The messages of the device must be perceptible even if it is installed in a control cabinet.
The devices is not designed for use in residential areas and may not provide sufficient
protection for radio reception there.
Any other use than that described in this manual is regarded as improper.
Areas of application
•Insulation fault location in AC, 3(N)AC and DC IT systems
•Main circuits and control circuits in industrial plants and ships
•Diode-decoupled DC IT systems in power plants
•Systems for medical locations
Standards
The standard for unearthed power supplies (IT systems)
DIN VDE 0100-410 (VDE 0100- 410):2018-10 (IEC 60364-4-41:2005, modified + A1:2017,
modified)
requires that the first insulation fault is to be eliminated with the shortest practicable
delay. EDS systems enable fast localisation of this insulation fault.
2 EDS44x_D0020 _ _D_XXEN/ .2023

ISOSCAN® EDS440 and EDS44
Operating principle of the EDS system
When an insulation monitoring device detects an insulation fault,
it starts the insulation fault location.
In the event of a first insulation fault, an undefined residual
current flows in IT systems, which is primarily defined by the
system leakage capacitances and the value of the insulation fault.
The basic idea of insulation fault location is therefore to generate a
defined locating current IL that flows through the insulation fault.
The locating current is driven by the system voltage and can be
located in the faulty outgoing circuit using the measuring current
transformer.
The locating current is generated by the locating current injector.
It is limited in amplitude and time. The amplitude depends on the
size of the existing insulation fault and the system voltage. It is
limited depending on the settings.
The locating current flows from the locating current injector via
the live lines to the insulation fault location taking the shortest
route. From there, it flows through the insulation fault and the
earth conductor back to the locating current injector. This locating
current pulse is detected by the measuring current transformers
on the insulation fault path and signalled by the connected
insulation fault locator.
System variants
The devices ISOSCAN® EDS440 and EDS44 differ depending on their response sensitivity. EDS440 is suitable for main circuits. EDS44
can be used in control circuits and in circuits in medical locations.
-L -S -LAB-4 -LAF-4
EDS440 Channel LED
BS bus
IΔL = 2…10 mA
Main circuits
Digital in uts and out uts
No channel LED
BB bus
IΔL = 2…10 mA
Main circuits
No internal voltage su ly
Channel LED
BS bus
IΔL = 10 mA 2)
Main circuits
Digital in uts and out uts
EDS441 Channel LED
BS-Bus
IΔL = 0.2…1 mA
Control circuits
Digital in uts and out uts
No channel LED
BB bus
IΔL = 0.2…1 mA
Control circuits
No internal voltage su ly
Channel LED
BS-Bus
IΔL = 0.2…1 mA 1)
Control circuits
W…AB current transformers
Digital in uts and out uts
) High response sensitivity with large system leakage capacitances
2) In combination with CTAF...SET series measuring current transformers
EDS44x_D0020 _ _D_XXEN/ .2023 3

ISOSCAN® EDS440 and EDS44
Display elements EDS44…-S
ON
Status LED
ON Flashes: Starting rocess; hourly transformer connection test
Lights u : o erational
Operating and display elements EDS44…-L
-1
>3s
ADDR.
RESET
+1
+10
TEST
CHANNELS / ADDR.
12
11109
87
345621
+10 +20 +40
Addr. Mode
n
∆
I
ALARM
L
∆
I
ALARM
SERVICE
COM/ADDR.
ON
Status LEDs
ON Flashes: Starting rocess; hourly transformer connection
test
Lights u : o erational
COM/ADDR. Flashes quickly: device communicates via RS-485
interface
Flashes: insulation fault location (LED indicate the ulse
of the locating current injector:
ulse = on; ause = off. In LAB rocedure, the ulse can
last one minute.)
SERVICE Lights u : device error; connection fault of the measuring
current transformers; error message e.g. due to low-
frequency residual currents, external magnetic fields, etc.
ALARM IΔL Lights u : main alarm, insulation fault on one of the
measuring channels (EDS function)
ALARM IΔn Lights u : res onse value for residual currents is
exceeded.
Channel LEDs 1 to 12
CHANNELS /
ADDR.
Lights u : insulation fault on the res ective measuring
channel or residual current alarm
Flashes slowly (1 Hz): connection fault of the measuring
current transformer
Flashes quickly (2 Hz): interference during insulation fault
location
Addr. Mode Indication of the resent tens counter by means of the
channel LEDs 10, 11 and 12
Operating buttons
TEST
+10
Starts self test.
In address assignment mode: increase address in ste s of
ten.
RESET
+1
Resets the fault memory. Only ossible if the fault
memory is activated and a fault is no longer detected.
In address assignment mode: increase address in ste s of
one.
ADDR.
–1
Long ress (>3 s): activates the address assignment
mode.
In address assignment mode: decrease address in ste s of
one.
4 EDS44x_D0020 _ _D_XXEN/ .2023

ISOSCAN® EDS440 and EDS44
Connection to the voltage supply
A1 A2
12 3 4 5 6 7 8 9 10 11 12
L
Us =AC/DC 24...240 V
A1/+ A2/–
L1/+
L2/–
Voltage supply back-up fuse
If the device is supplied via an external power supply unit,
the back-up fuse Fback-up at connection “A /+ A2/−” must be
selected in such a way that the feeding power supply unit is
able to trip the DC-compatible back-up fuse.
Example:
A back-up fuse of 650 mA/T is recommended when using a
24 V power supply unit (min. A).
Connection of the X1 interface (I1 I2 A B M+ ...)
BA
M+
BA
I2
I1
23 24
13 14
OFF ON
R
I1
I2 A B
A B
M+
I1 In ut 1 M+ dig. current out ut
I2 In ut 2 Ground
ARS-485 A (in ut) ARS-485 A (out ut)
BRS-485 B (in ut) BRS-485 B (out ut)
The EDS44…-L is connected via the X plug.
The EDS44…-S does not feature an X interface and can
only be connected via the BB bus.
Connection of the relays
BA
M+
BA
I2
I1
23 24
13 14
OFF ON
R
23 24
13 14
13 23
Alarm relay 1 14 n/o contact Alarm relay 2 24 n/o contact
BS bus termination
BA
M+
BA
I2
I1
23 24
13 14
OFF ON
R
OFF ON
R
Activating a terminating resistor to define the first and the last
device in the bus system.
OFF All devices between the first
and the last device in the bus
ON First and last device in a bus
Connection of the X2 interface (k1-12/l1-12)
A1 A2
12 3 4 5 6 7 8 9 10 11 12
L
l 1 l 12l 11l 2 l 10l 9l 8l 7l 6l 5l 4l 3
k 1 k12k11k 2 k10k 9k 8k 7k 6k 5k 4k 3
l1 Measuring current
transformer 1
k1
l2 Measuring current
transformer 2
k2
l3 Measuring current
transformer 3
k3
l4 Measuring current
transformer 4
k4
………
l12 Measuring current
transformer 12
k12
Cable lengths of the measuring current transformers
In tall the mea uring current tran former according to the
in truction in the re pective data heet of the mea uring
current tran former. When connecting, ob erve the maximum
cable length .
EDS44x_D0020 _ _D_XXEN/ .2023 5

ISOSCAN® EDS440 and EDS44
Connection of CTAC… series measuring current transformers
For insulation fault location, the measuring current transformers
of the CTAC… series are used.
A1/+ A2/-
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
Type A
CTAC 1
kl
CTAC 2
kl
l1 k1 l2 k2
l k l k
CTAC… series measuring current transformers
Terminals and 2 as well as terminals 3 and 4 of the
measuring current transformer are bridged internally.
The connections k and l must not be interchanged on the
EDS44….
Live conductors and measuring current transformers
Ensure that all live conductors are routed through the
measuring current transformer. Do not route any existing
PE conductors or shields of shielded cables through the
measuring current transformer! Standard measuring
current transformers are not suitable for the EDS44…
system and must not be used. An accurate measurement
result can only be obtained when these instructions are
observed.
For further information regarding measuring current
transformers, refer to the respective data sheets.
Connection of CTAF…SET series measuring current
transformers to EDS440-LAF-4
For insulation fault location, the measuring current transformers
of the CTAF…SET series are used.
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
l1 k1 l2
Typ A
k2
2
1
1
2
Locating current
The EDS440-LAF-4 operates exclusively with a locating
current > 0 mA.
Connection of measuring current transformer CTBC… to
EDS441-LAB-4
CTXS…
CTBC…
24V GND
k
l
1 m
2.5 m
5 m
10 m
50 mm
250 mm
EDS441-LAB STEP-PS
power supply
CTUB102
24V
GND
S1(k)
S2(l)
Locating current
The EDS44 -LAB-4 operates exclusively with a locating
current of max. 25 mA. Therefore, selecting the current
range >500 mA on the current transformer is not suitable
for measuring locating currents <25 mA.
6 EDS44x_D0020 _ _D_XXEN/ .2023

ISOSCAN® EDS440 and EDS44
Connection to a 3(N)AC system
A BA B
iso685-D-P EDS44…-L/-S
Un
L1
L2
L3
N
PE
USUS
A1/+
A2/-
21 22 24
11 12 14
L1/+
L2 L3/- KE E
iso685
ISOMETER
®
RX2
X1
l1 l2 l3 A B
EKEL3/-L2
L1/+A1/+ A2/-
EDS440
ISOSCAN
®
I
ΔL
I
Δn
13 14 23 24
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
X1
l1 l2 A B
A1/+ A2/-
A1/+ A2/- l1 k1 l2 k2
1
2
2
3
4
Measuring current transformers
2to the loads
3BB bus for communication to and supply of EDS44…-S
4BS bus for communication from iso685(W)-…-P to EDS44…-L
USConnection of the supply voltage only to EDS44…-L
EDS44x_D0020 _ _D_XXEN/ .2023 7

ISOSCAN® EDS440 and EDS44
Connection to a DC system
A BA B
iso685-D-P EDS44…-L/-S
L+
L–
PE
Un
USUS
A1/+
A2/-
21 22 24
11 12 14
L1/+
L2 L3/- KE E
iso685
ISOMETER
®
RX2
X1
l1 l2 l3 A B
EKEL3/-L2
L1/+A1/+ A2/-
EDS440
ISOSCAN
®
I
ΔL
I
Δn
13 14 23 24
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
X1
l1 l2 A B
A1/+ A2/-
A1/+ A2/- l1 k1 l2 k2
1
2
2
3
4
Measuring current transformers
2to the loads
3BB bus for communication to and supply of EDS44…-S
4BS bus for communication from iso685(W)-…-P to EDS44…-L
USConnection of the supply voltage only to EDS44…-L
8 EDS44x_D0020 _ _D_XXEN/ .2023

ISOSCAN® EDS440 and EDS44
Connection to an AC system
A BA B
iso685-D-P EDS44…-L/-S
Un
L1
L2
PE
USUS
A1/+
A2/-
21 22 24
11 12 14
L1/+
L2 L3/- KE E
iso685
ISOMETER
®
RX2
X1
l1 l2 l3 A B
EKEL3/-L2
L1/+A1/+ A2/-
EDS440
ISOSCAN
®
I
ΔL
I
Δn
13 14 23 24
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
X1
l1 l2 A B
A1/+ A2/-
A1/+ A2/- l1 k1 l2 k2
1
2
2
3
4
Measuring current transformers
2to the loads
3BB bus for communication to and supply of EDS44…-S
4BS bus for communication from iso685(W)-…-P to EDS44…-L
USConnection of the supply voltage only to EDS44…-L
EDS44x_D0020 _ _D_XXEN/ .2023 9

ISOSCAN® EDS440 and EDS44
Connection example: ISOMETER® iso685-D-P EDS440-S IOM441-S and EDS440-L
A BA B
A1/+ A2/-
RX2 11 12 14 21 22 24
L1/+
L2 L3/- KE E
X1
l1 l2 l3 A B
iso685
ISOMETER
®
EDS440
ISOSCAN
®
I
ΔL
I
Δn
X1
l1 l2 A B
13 14 23 24
A1/+ A2/-
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
EDS440
ISOSCAN
®
I
ΔL
I
Δn
13 14 23 24
l1
k1
l2
k2
l3
k3
l4
k4
l5
k5
l6
k6
l7
k7
l8
k8
l9
k9
l10
k10
l11
k11
l12
k12
Us
IOM441
123144 124104103 1139384 947473 83
6354 644443 533324 341413 23
13 14
L1
L2
L3
N
PE
UsUs
Un
iso685-D-P EDS44…-S IOM441 EDS44…-L
KEL3/-L2 E
A1/+ L1/+A2/- A1/+ A2/-
l1 k1 l2 k2l1 k1 l2 k2
Communication between iso685-...-P and EDS44...-L runs exclusively via BS bus (RS-485).
0 EDS44x_D0020 _ _D_XXEN/ .2023
Este manual sirve para los siguientes modelos
12
Otros manuales de Relé de Bender

Bender
Bender VME421H Manual de usuario

Bender
Bender CMD420 Manual de usuario

Bender
Bender UMS420 Manual de usuario

Bender
Bender IOM441-S Manual de usuario

Bender
Bender cme420 Manual de usuario

Bender
Bender RCM470LY Manual de usuario

Bender
Bender IOM441-S Manual de usuario

Bender
Bender cme420 Manual

Bender
Bender cme420 Manual de usuario

Bender
Bender LINETRAXX VMD461 Manual de usuario




















