Beijer Electronics GL-9089 Manual de usuario

Quick Start Guide
Modbus TCP, Ethernet IP network
adapter, GL-9089 and GN-9289
SUEN00416 –
How to set IP address, Subnet Mask and Gateway on
GL-9089 and GN-9289

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
2 (11)
Normal.dotm, 2020-09-09
1Function and area of use
In this document we show how to set IP address, Subnet Mask and Gateway for
G-Series network adapters GL-9089 and GN-9289.
2About this Startup document
This Startup document should not be considered as a complete manual. It is an aid to be
able to startup a normal application quickly and easily.
This Start Up document should not be considered as a complete manual. It is an aid to be
able to start up a normal application quickly and easily.
Use the following software and drivers in order to obtain a stable application:
In this document we have used following hardware and software
•Modbus TCP/Ethernet IP network adapter light GL-9089
•Modbus TCP/Ethernet IP network adapter GN-9289
•BootpServerVer1000_Beijer Link to BootP
•Windows 10 64 bit
For further information we refer to
•GL-9089 Manual Link
•GN-9289 Manual Link
For further information refer to
•Manual name/number
•Beijer Electronics knowledge database, HelpOnline
This document and other Startup documents can be obtained from our homepage.
documents.
Copyright © Beijer Electronics, 2023
This documentation (below referred to as ‘the material’) is the property of Beijer Electronics. The holder or user has a non-
exclusive right to use the material.
The holder is not allowed to distribute the material to anyone outside his/her organization except in cases where the material is
part of a system that is supplied by the holder to his/her customer.
The material may only be used with products or software supplied by Beijer Electronics.
Beijer Electronics assumes no responsibility for any defects in the material, or for any consequences that might arise from the use of
the material.
It is the responsibility of the holder to ensure that any systems, for whatever applications, which is based on or includes the
material (whether in its entirety or in parts), meets the expected properties or functional requirements.
Beijer Electronics has no obligation to supply the holder with updated versions.

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
3 (11)
Normal.dotm, 2020-09-09
3Table of Contents
1Function and area of use................................................................................. 2
2About this Startup document............................................................................ 2
3Table of Contents.......................................................................................... 3
4Setup network address in GL-9089 and GN-9289 ................................................... 4
Default network settings .......................................................................... 4
Use BOOTP server................................................................................... 4
5About Beijer Electronics ............................................................................... 11
Contact us ..........................................................................................11

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
4 (11)
Normal.dotm, 2020-09-09
4Setup network address in GL-9089 and GN-9289
Setting of the IP address is made through BOOTP.
Default network settings
Use BOOTP server
BOOTP is a standard protocol that can be used to configure the network settings on a
GL-9089 and GN-9289.
Sometimes it’s required to disable all other network devices besides the one being used to
configure the GL-9089/GN-9289.
In some rare case the firewall needs to be disabled, select “Turn off…” on all networks and
push “OK”.
Remember to reactivate the firewall after the IP address setting is done!
Default Setting
IP Address
192.168.1.100
Subnet Mask
255.255.255.0
Gateway
0.0.0.0
Active

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
5 (11)
Normal.dotm, 2020-09-09
There could be security software (like antivirus programs) that might need to be temporarily
disabled.
In some cases when cycling the power of the network adapter, without using a switch between
the PC and network adapter, the BOOTP application will loose its reference to the ethernet
port. The best and recommended way is to use a switch between the PC and the device.

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
6 (11)
Normal.dotm, 2020-09-09
BootP, method 1
1. Connect the PC with the GL-9089/GN-9289 over Ethernet.
2. Set a fixed IP address on the PC, same subnet as the GL-9089/GN-9289 is to be changed
to. The IP address for the PC should not be assigned automatically (DHCP).Se section 4.2.
part 1.
3. Always use the latest version of Beijer BOOTP server (included in IOGuidePro or extracted
tool).
4. Run IOGuidePro, and select menu Tools > Bootp Server, or start the BOOTP tool from
folder. Alternative run the BOOTP server separately (BootpSvr.exe).
5. When the BOOTP Server is launched and to allow G-series device in present version of
IOGuidePro. Make sure that option ”Show Beijer device only” is unchecked!
Push the “Add New Device” button and enter the MAC address and desired IP address,
subnet and gateway. Select the network interface that the GL-9089/GN-9289 is connected
to.
Push “Ok” and “Start Bootp”.

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
7 (11)
Normal.dotm, 2020-09-09
6. Power OFF the GL-9089/GN-9289 and set DIP switch 9 to ON (BOOTP).
7. Power on the GL-9089/GN-9289 device, and the device will get the new IP address from
the BootP server, it appears in the upper window.
8. “Stop Bootp” and reset DIP switch 9 to OFF, and reboot the GL-9089/GN-9289 device.
9. If the IP is set to a different subnet then change the IP address of your computer
accordingly.
10. Try to ping the device with new IP address.
11. Close the BOOTP Server.

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
8 (11)
Normal.dotm, 2020-09-09
BootP, method 2
1. Connect the PC with the GL-9089/GN-9289 over Ethernet.
2. Set a fixed IP address on the PC, same subnet as the GL-9089/GN-9289 is to be changed
to. The IP address for the PC should not be assigned automatically (DHCP). Se section 4.2.
part 1.
3. Always use the latest version of the Beijer BOOTP server included in IOGuidePro or
extracted tool.
4. Run IOGuidePro and select menu Tools > Bootp Server, or start the BOOTP tool from
folder. / Alternative run the Bootp server separately (BootpSvr.exe).
5. When the BootP Server is launched and to allow M-series device in present version of
IOGuidePro, make sure that ”Show Beijer device only” is unchecked!
6. Press “Start Bootp”.
7. Power OFF the GL-9089/GN-9289 and set DIP switch 9 to ON (BOOTP).

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
9 (11)
Normal.dotm, 2020-09-09
8. Power on the GL-9089/GN-9289 device, and the device will be shown in the BootP server.
Double click on one of the marked rows above.
The MAC address is default entered, type required IP address, Subnet and Gateway. Select the
correct “Interface”, PC:s Ethernet connection to the GL-9089/GN-9289 and push “Ok”.
9. Now press “Stop BootP”.
10. Reset the DIP switch 9 to OFF, and reboot the GL-9089/GN-9289 device.
11. If the IP is set to a different subnet then change the IP address of your computer
accordingly.

GL-9089 and GN-9289 - IP address, Subnet and Gateway Setting SUEN00416 2023-03
10 (11)
Normal.dotm, 2020-09-09
12. Try to ping the device with new IP address.
13. Close the BOOTP Server.
Note!
MODBUS/TCP IP –Address Setup
If the adapter BOOTP/DHCP enabled (DIP Pole#9 ON), the adapter sends
BOOTP/DHCP request message of 20 times every 2sec. If BOOTP/DHCP sever does
not response, the Adapter applies its IP Address with EEPROM (Latest saved IP
Address).
Este manual sirve para los siguientes modelos
2
Tabla de contenidos
Otros manuales de Adaptador de Beijer Electronics

Beijer Electronics
Beijer Electronics G Series Manual de usuario

Beijer Electronics
Beijer Electronics GL-9084 Manual de usuario

Beijer Electronics
Beijer Electronics GL-9086 Manual de usuario

Beijer Electronics
Beijer Electronics DeviceNet GN-9212 Manual de usuario

Beijer Electronics
Beijer Electronics IFC PBDP Manual de usuario

Beijer Electronics
Beijer Electronics G Series Manual de usuario