IMPORTANT
PLEASE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE
INSTALLING THE BAXI PREMIER PLUS WATER HEATER. INCORRECT
INSTALLATION MAY INVALIDATE GUARANTEE.
THE BAXI PREMIER PLUS WATER HEATER MUST BE INSTALLED BY A
QUALIFIED INSTALLER IN ACCORDANCE WITH LOCAL PLUMBING, BUILDING
AND ELECTRICAL REGULATIONS
THIS APPLIANCE CAN BE USED BY CHILDREN AGED FROM 8 YEARS AND ABOVE
AND PERSONS WITH REDUCED PHYSICAL SENSORY OR MENTAL CAPABILITIES
OR LACK OF EXPERIENCE AND KNOWLEDGE IF THEY HAVE BEEN GIVEN
SUPERVISORY OR INSTRUCTION CONCERNING USE OF THE APPLIANCE IN A
SAFE WAY AND UNDERSTAND THE HAZARDS INVOLVED. CHILDREN SHALL NOT
PLAY WITH THE APPLIANCE. CLEANING AND USER MAINTENANCE SHALL NOT
BE MADE BY CHILDREN WITHOUT SUPERVISION.
Also:
- Water may drip from the discharge pipe of the pressure-relief device and this pipe
must be left open to the atmosphere;
-The pressure-relief device is to be operated regularly to remove lime deposits and to
verify that it is not blocked;
- How hot water can be drained. (see page 10 for details)
TECHNICAL SPECIFICATIONS
Rated pressure: 1.5MPa (15 bar) Max*
Test pressure (hydraulic): 2.3MPa (23 bar)
Minimum recommended supply pressure: 0.15MPa (1.5 bar)
See Table 2, page 4 for a full specication list.
* A TPR (Temperature and Pressure Relief) valve between 8 Bar and 15 bar must be
installed. These tanks are supplied with a 10 Bar TPR.
1. IMPORTANT INSTALLATION POINTS
1.1 The BAXI Premier Plus water heater MUST be tted with a pressure relief valve
rated at 8 bar. FAILURE TO PROVIDE ADEQUATE PRESSURE RELIEF WILL
INVALIDATE ANY GUARANTEE AND LEAD TO A DANGEROUS INSTALLATION.
1.2 Where the inlet pressure exceeds 6 bar a pressure reducing valve (set at max.
6 bar) should be tted to the inlet supply to the heater. This MUST NOT be tted
between the pressure relief valve and the water heater (see Diagram 3, page 6).
1.3 A Check (Non-return) Valve should be tted to the inlet supply to the water heater.
This MUST NOT be tted between the pressure relief valve and the water heater.
(see Diagram 3, page 6). This may be provided as part of the inlet security group.