Commissioning Guide
Wireless Emergency Lighting
GR-7600/V2

COPYRIGHT©
Thispublication,orpartsthereof,maynot
bereproducedinanyform,byanymethod,
foranypurpose.
AutronicaFireandSecurityASandits
subsidiariesassumenoresponsibilityfor
anyerrorsthatmayappearinthe
publication,orfordamagesarisingfromthe
informationinit.Noinformationinthis
publicationshouldberegardedasa
warrantymadebyAutronicaFireand
SecurityAS.Theinformationinthis
publicationmaybeupdatedwithoutnotice.
Productnamesmentionedinthis
publicationmaybetrademarks.Theyare
usedonlyforidentification.

Commissioning Guide – 116-GR-7600/V2 Wireless Emergency Lighting
‐3‐
WEL‐Commissioning‐Handbook‐eng.docx
1. INTRODUCTION.........................................................................................................................................5
2. INSTALLING SOFTWARE APPLICATION 116-GR-7600/V2............................................................5
3. SPECIFICATIONS AND TERMS...........................................................................................................11
4. USER MANAGEMENT............................................................................................................................13
5. COMMISSIONING....................................................................................................................................14
5.1Before starting.....................................................................................................................................14
5.2Spectrum Analyzer.............................................................................................................................16
5.3Connecting 116-GR-7603/V2 Ethernet + Wifi Gateway..............................................................18
ForEthernetconnectivity:................................................................................................................20
ForWi‐Fi(WPA2/PSK)connectivity:.................................................................................................20
ForWi‐Fi(WPS)connectivity:.........................................................................................................s21
5.4Connecting a 116-GR-7607/V2 or 116-GR-7605/V2 as USB Gateway....................................22
5.5Network detection and configurations..........................................................................................22
5.5.1Network configuration wizard (single network)........................................................................23
5.5.2Easy Commissioning (multiple networks)..................................................................................26
5.5.3Easy Commissioning (adding new devices)..............................................................................28
5.6Edit Names...........................................................................................................................................29
5.6.1Edit Gateway name........................................................................................................................29
5.6.2Edit name of a wireless device...................................................................................................29
5.7Creating Floor Plans..........................................................................................................................30
5.8Setting Zones for emergency luminaires.....................................................................................32
5.9Configuring Wireless In/Out units triggers..................................................................................33
6. RESET SYSTEM STATUS / CLEAR EVENTS....................................................................................34
7. SYSTEM SETTINGS................................................................................................................................35
7.1General page........................................................................................................................................35
7.2Test page (schedule Lamp & Battery test)...................................................................................36
7.3Notifications page..............................................................................................................................36
7.4E-mails page........................................................................................................................................37
7.5Tablet page...........................................................................................................................................37
7.6Modbus page.......................................................................................................................................38

Commissioning Guide – 116-GR-7600/V2 Wireless Emergency Lighting
‐4‐
WEL‐Commissioning‐Handbook‐eng.docx
8. BROADCAST COMMANDS / RUN TESTS.........................................................................................39
9. IMPORTANT NOTES...............................................................................................................................41

Commissioning Guide – 116-GR-7600/V2 Wireless Emergency Lighting
‐5‐
WEL‐Commissioning‐Handbook‐eng.docx
1. INTRODUCTION
This guide provides instructions regarding commissioning wireless emergency
lighting system 116-GR-7600/V2 – by Autronica. Prior to commissioning, the
installation of the wireless emergency lighting shall be fulfilled in accordance with the
corresponding Quick Installation Guide.
IMPORTANT: Before commissioning the wireless emergency system there must be an
existing running network. The commissioning requires a high degree of network
competence.
2. INSTALLING SOFTWARE APPLICATION
116-GR-7600/V2
In order to use a Windows PC as the master PC of the wireless emergency lighting system,
start by installing the software application.
116-GR-7600/V2 software minimum PC requirements:
Windows 10 64bit
3GB RAM
8GB free storage space
CPU dual core 1,3GHz
Ethernet or Wi-Fi connectivity
For the master PC, which is responsible of monitoring and controlling wireless network traffic
and holding the system database, please do install all pre-selected packages (full installation).
1. 2.

Commissioning Guide – 116-GR-7600/V2 Wireless Emergency Lighting
‐6‐
WEL‐Commissioning‐Handbook‐eng.docx
3. 4.
Note: for client PCs that their purpose is to monitor the wireless installation remotely, install
only the “WEL User Interface” and “.NET Framework”, as all other packages are needed for
the master PC only.
Launch “WelManagement” from the desktop shortcut. At first launch, the application settings
window will show up. A certificate is needed to be created in order to provide safe
communication of the “API” service. If there was no previous certificate installed on this master
PC, press the “Create Certificate” button.
Then follow the steps as shown below:

Commissioning Guide – 116-GR-7600/V2 Wireless Emergency Lighting
‐7‐
WEL‐Commissioning‐Handbook‐eng.docx
1. 2.
3. 4.
5. 6.

Commissioning Guide – 116-GR-7600/V2 Wireless Emergency Lighting
‐8‐
WEL‐Commissioning‐Handbook‐eng.docx
7.
The same certificate (which you can copy on a USB flash drive) can be used to other client
devices for remote access. For remote access, choose “Install Certificate” and import the
certificate from the USB flash drive. On the application settings for the remote access PC, the
target IP for the Database and the Data Receiver must be the IP of the master PC, while the
“User Interface” IP must be the remote PC’s IPv4 address.
After installation of the certificate, click on “Submit”.
Then you will be prompted to restart the PC.
After restarting, all processes needed for the wireless lighting system will run on the
background in real time, even when you are not using User Interface.

Commissioning Guide – 116-GR-7600/V2 Wireless Emergency Lighting
‐9‐
WEL‐Commissioning‐Handbook‐eng.docx
Important Notes:
The master PC which runs the “116-GR-7600/V2” software application must be
operating uninterruptedly (energy saving plan disabled).
To maintain communication when mains power is down, connect this master
PC and the “116-GR-7603/V2” Gateways to a UPS.
The IPs’ that are used for, “Receiver” and “Database” must be static IPv4.
Therefore the master PC must use a static IP permanently.
“WelAPI”, “WelDbmaker”, “WelReceiver” and “WelModbus” are 4 essential
services running in the background. Do not block or stop these services by
any means.
Consult an IT technician for local network addressing if needed.
Now, when launching the “WelManagement” icon, the user login screen will appear (User
Interface).
Default administrator username: admin
Default administrator password: 1000
After the first login you are prompted to enter new “Password” and “Recovery Code”. These
login credentials must be kept safe, as they are used only by the administrator. Use at least
an 8-digit password and also avoid using the same value for the recovery code, as the system
will reject it.

Commissioning Guide – 116-GR-7600/V2 Wireless Emergency Lighting
‐10‐
WEL‐Commissioning‐Handbook‐eng.docx
After this you can login with your new password.
The system administrator has all privileges required to add, delete, monitor and control every
segment of the system (users, gateways, devices, settings, etc).
Use this account, or create a new one with “administrator” privileges to continue with the
commissioning procedure.
(see: 4. User Management for more information)
Otros manuales para GR-7600/V2
1
Tabla de contenidos
Otros manuales de Equipo de iluminación de Autronica
Manuales populares de Equipo de iluminación de otras marcas

Qazqa
Qazqa Suplux SL 3 Black 103062 Manual de usuario

Commercial Electric
Commercial Electric 54568141 Manual de usuario

CREE LIGHTING
CREE LIGHTING 304 Series Manual de usuario

Goobay
Goobay 49867 Manual de usuario

ECOMAN ITALIA
ECOMAN ITALIA LED T8 Manual de usuario

Alkalite
Alkalite Krypton KT-81 Manual de usuario