Auspex Fire Manual de usuario

Auspex Fire
Manual
Edition 1 |2021
auspex.com.au

ii |Auspex Fire Manual
The Auspex Fire pipe and
fitting system provides a
revolutionary solution to meet
new standard requirements in
the fire industry.

From 2019, legislation now requires all residential buildings
4 stories or more to be sprinkler protected. The National
Construction Code oers significant reliability and cost saving
advantages by referencing the new FPAA101D PEX pipe
sprinkler system, which permits sprinklers to be plumbed o
the already required domestic riser.
The PEX pipe “101D” system is by far the most cost-eective
option for installers and developers of these residential
buildings. This eliminates the need to provide dedicated
sprinkler and hydrant service tappings, fire pumps and alarm
equipment. Utilising drinking water supplied by a WaterMark
approved piping system significantly reduces backflow
hazards to the community and now eectively eliminates the
possibility of sprinkler systems being inadvertently shut o.
The Auspex system was used for tests conducted by
CSIRO for the Fire Authorities at the very beginning of the
development of the new FPAA101D system. Since then,
Auspex has continued to work on developing a suite of
dedicated piping and fixing arrangements specifically for
sprinkler head fit o, in all relevant pipe diameters. This
ensures installers have the easiest and fastest means of
fitting o sprinklers in the wall or ceiling that is compliant
with the relevant Codes and Standards.
Residential sprinkler
Sanitary facility
Network utility operator
town main
Below ground street
isolation valve
Water supply backflow assembly
Main water meter
Pumpset
SOU water meters
Sprinkler / Domestic
floor isolation valve
Backflow prevention
device
Riser
Level 1
SOU 2
SOU 1
Level 2
Auspex Fire Manual | 1
Layout schematic

2| Auspex Fire Manual
Auspex Fire Pipes
Auspex Fire pipe is unique in many ways.
• PEX pipe with integrated red stripes – no need for the
additional expense or work of marking tape
• PN 20 pipe
• Sizing up to 32mm in PEX with the ability to join onto
DuoPEX Water pipe up to 63mm
• Compatible with the existing Auspex fittings and tooling
• Australian manufactured
• Stocked by Reece
• 25+ years of history in the Australian market
• SDR 9 which has a better flow rate than SDR 7.4 pipe

Auspex Fire Manual | 3
Auspex Fire Fittings
• Proven Auspex jointing system with over 25 years in the
Australian plumbing industry
• Using the complete Auspex fitting product range
• Specialised sprinkler connections developed providing
greater options to installers
• Solid brass construction for reliable fixing
• Standard Auspex tooling for dimensions up to 32mm,
hand tools and battery tool options
• DuoPEX Water conversion fittings allows the installation
to be included up to 63mm
• Rigid mounting clip allows versatile flexibility and
confidence of installation
Auspex Fire 25mm x
>B< Press DN25
Elbow Adaptor
APF28052525
Auspex Fire 25mm x
Auspex Fire 25mm x
>B< Press DN25
Tee Adaptor
APF28252525
Auspex Fire 25mm x
Auspex Fire 25mm x
>B< Press DN25
Tee Adaptor
APF28252525
Auspex 25mm x
25mm x 25mm Tee
AP03252525
Auspex Fire PEX100
25mm Straight Pipe
XAP422505RS
Auspex 25mm x
25mm Elbow
AP052525
Side Mount Bracket
APF2890B

4| Auspex Fire Manual
Water Pressure Loss
Calculation of Potable Water – Principals
The following tables show Pressure Loss for Auspex Fire pipe
at a fluid temperature of 10°C.
Pipe
Size 20mm 25mm 32mm
Flow
Velocity
(m/s)
Volumetric
Flow
(L/s)
Pressure
Loss
(kPa)
Volumetric
Flow
(L/s)
Pressure
Loss
(kPa/m)
Volumetric
Flow
(L/s)
Pressure
Loss
(kPa)
0.5 0.09 0.26 0.15 0.20 0.24 0.15
0.6 0.11 0.37 0.18 0.28 0.28 0.21
0.7 0.13 0.50 0.20 0.36 0.33 0.28
0.8 0.14 0.63 0.23 0.47 0.38 0.36
0.9 0.16 0.78 0.26 0.59 0.43 0.45
1.0 0.18 0.96 0.29 0.72 0.47 0.55
1.2 0.21 1.34 0.35 1.00 0.57 0.76
1.4 0.25 1.78 0.41 1.33 0.66 1.01
1.6 0.29 2.28 0.47 1.71 0.76 1.30
1.8 0.32 2.83 0.53 2.12 0.85 1.61
2.0 0.36 3.43 0.59 2.58 0.95 1.96
2.5 0.44 5.20 0.73 3.90 1.18 2.96
3.0 0.53 7.29 0.88 5.45 1.41 4.14
3.5 0.62 9.73 1.00 7.28 1.65 5.51
4.0 0.71 12.43 1.17 9.31 1.89 7.06
4.5 0.80 15.44 1.32 11.58 2.12 8.79
5.0 0.89 18.81 1.46 14.08 2.36 10.68
Size Mean OD Min Wall Max Mean ID
20mm 20.0 2.3 15.7
25mm 25.0 2.8 19.7
32mm 32.0 3.7 24.5
Factor 1.20 1.14 1.10 1.05 1.02 0.98 0.95
Water °C 20 30 40 50 60 80 90

16mm
20mm
25mm
32mm
0.001
0.01
0.1
1
10
100
1000
0.001 0.010.1 1.0
0.50.05
Pressure Loss KPa/metre of Pipe
Flow Litres/Second
Flow velocity Metres/Sec
Water Temperature +70°C
Roughness coecient 0.0005mm
3.0
2.5
2.0
1.0
1.25
0.25
1.50
4.0
0.10
0.20
0.15
0.30
0.40
0.50
0.60
Auspex Fire Manual | 5

6| Auspex Fire Manual
Auspex Fire Fitting Pressure Drop
Pressure losses due to individual resistances can be
calculated based on the loss coecients and based on the
equivalent pipe lengths of the individual resistances.
These value equivalents are then added to the pipe lengths
of the respective pipe sections to then calculate the
total resistance.
Individual Resistance Graphic
Symbol
Fittings Equivalent
Pipe Length (FEPL)
20 25 32
Coupling 0.38 0.55 0.5
Elbow
(90°) 3.8 2.6 3.0
Tee,
Run Flow
Separation
0.41 0.55 0.6
Tee,
Branch
Flow
Separation
4.26 2.8 3.0
Tee,
Transition
Flow
Separation
4.26 2.8 3.0
Reduction
14.0
(32mm)
4.6
(25mm)
2.8 –
Pressure Losses Due to Individual Resistances
(Standard Auspex Fittings)

Auspex Fire Manual | 7
Pressure Losses Due to Individual Resistances
(Auspex Fire Fittings)
a. The symbol "V" for flow velocity defines the location
of the proper reference velocity in the fitting and
connecting piece
b. For reduced tees, the resistance value of the similar tee
is assumed with the smallest dimension of the reduced
tee for the flow path to be calculated
General: The loss coecient is assigned in each case to
the volumetric flow (partial flow), which is indicated in the
diagram with the symbol "V".
Individual Resistance Graphic
Symbol
Fittings Equivalent
Pipe Length (FEPL)
20 25 32
Threaded
Lugged
Elbow
4.6 4.8 9.2
PEX to Cu
Lugged
Elbow
1.5 1.2 2.0
Threaded
Centre Tee,
Run Flow
Separation
0.6 0.6 0.7
Threaded
Centre Tee,
Branch Flow
Separation
4.5 4.7 10.0
Cu Centre Tee,
Run Flow
Separation
0.9 0.9 0.9
Cu Centre Tee,
Branch Flow
Separation
4.0 3.9 4.1
Cu Centre Tee
(Reducing),
Run Flow
Separation
0.7 0.7 –
Cu Centre Tee
(Reducing),
Branch Flow
Separation
4.7 11.1 –

8| Auspex Fire Manual
Step 1.
Measure the pipe to the
correct length and using a
secateur-type pipe cutter,
cut the pipe squarely and
remove any burrs. The end
of the pipe may need to be
freshly cut to ensure smooth
passage for the fitting.
Do not use a hacksaw.
Step 2.
The pipe is pushed over the
barbed fitting and at the
same time under the crimp
ring. The fit should be firm.
If the joint feels sloppy or
hard to insert, check pipe
and fittings. Do not use
lubricants. Ensure the pipe
is visible in both crimp ring
witness holes.
witness hole
The witness holes should
be completely filled.
Making A Joint
Auspex fittings from 16mm-25mm use a copper crimp ring
connection and can be crimped with an Auspex manual tool
or a Rothenburger battery tool.
It is most important that the tool manual supplied with the
tool is read in its entirety and the user becomes familiar with
the maintenance, calibration and proper use of the tool.
The 32mm Auspex water fitting has a Stainless Steel
crimp ring and can only be crimped with the battery tool
using a DuoPEX jaw (see page 9). The DuoPEX jaws are
universal across all systems shown below.
Auspex 32mm water
fittings are defined by the
clear plastic holding ring
and are for use only with
the single layer Auspex
water pipe and multi-
layer Auspex Gas pipe.
DuoPEX Water
fittings are defined
by the blue plastic
holding ring and are
for use only with the
multi-layer DuoPEX
Water pipe.
DuoPEX Gas
fittings are defined
by the yellow
plastic holding ring
and are for use only
with the multi-layer
DuoPEX Gas pipe.
Tabla de contenidos
Manuales populares de Equipo de seguridad de otras marcas

Innova
Innova Xtirpa Manual de instrucciones

bolle SAFETY
bolle SAFETY B810 Manual de usuario

SHENZHEN FANHAI SANJIANG ELECTRONICS
SHENZHEN FANHAI SANJIANG ELECTRONICS A9060T Manual de usuario

Hiltron security
Hiltron security POWER8E Guía

Hatco
Hatco B-950P Manual de usuario

Sitec
Sitec TX MATIC Manual de usuario