ArcTiv Technologies EZ-PDU's Manual de usuario

OWNER’S MANUAL: EZ-PDU’S
1
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
OWNER’S MANUAL
EZ-PDU’s
EZ-PDU’s
™

OWNER’S MANUAL: EZ-PDU’S
2
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
TABLE OF CONTENTS
1. PRODUCT OVERVIEW …………………………………………………………………………………………………………………………………………………………
3
2. SAFETY INSTRUCTIONS ……………………………………………………………………………………………………………………………………………………….
4
3. NETWORK METERING .………………………………………………………………………………………………………………………………………………………..
5
3.1 NETWORK METER FUNCTIONS …………………………………………………………………………………………………………………………………………
5
3.2 INITIALIZATION …………………………………………………………………………………………………………………………………………………………………
6
3.3 HARDWARE SETTINGS ………………………………………………………………………………………………………………………………………………………
6
3.4 DAISY CHAIN SETTINGS …………………………………………………………………………………………………………………………………………………….
7
3.5 SOFTWARE OVERVIEW ……………………………………………………………………………………………………………………………………………………..
7
3.6 SNMP ACCESS …………………………………………………………………………………………………………………………………………………………………..
12
3.7 TELNET ACCESS …………………………………………………………………………………………………………………………………………………………………
16
4. SPECIFICATIONS ………………………………………………………………………………………………………………………………………………………………….
17
5. WARRANTY .…………………………………………………………………………………………………………………………………………………………………………
18

OWNER’S MANUAL: EZ-PDU’S
3
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
1. PRODUCT OVERVIEW
ArcTiv EZ-PDU’s are designed for easy configuration to meet the exact application requirements. Optional local or network
meters can be added during deployment or field-upgraded. Each PDU supports:
•Customizable with international and local plugs and outlets to the exact application requirement
•Compatible with DCIM’s via ModBus and SNMP communication
•Field upgradable network module
Benefits include:
Power Monitoring
Energy and power monitoring with 1% accuracy
Alarms
User-defined thresholds automate actions before overload
Remote Monitoring
Securely access real-time power consumption
Environmental Monitoring
Connects to rack sensors for system management
Daisy Chain
Connect up to 5 PDU’s with a single IP address to reduce cabling costs
Field Upgradeable
Upgrade the network module
Full Range
International and local plugs and outlets
Easy Installation
Tool-less 0U mounting compatible with Server and Network Racks
Safe Operation
Locking C13 outlets prevent accidental removal of power cables

OWNER’S MANUAL: EZ-PDU’S
4
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
2. SAFETY INSTRUCTIONS
•Keep the Basic & Metered PDU’s in a controlled indoor environment, away from moisture, temperature extremes,
flammable liquids and gasses, conductive contaminants, dust and direct sunlight.
•Before installing the PDU’s, check the existence of earth wires before the power supply.
•Check that the marked nominal voltage is the same as the service voltage in the country or region.
•Check that the supply is properly grounded and the power cord, plug and socket are in good condition.
•Check that the max power of the load equipment is less than the max output power of the PDU.
•Do NOT install the PDU where excessive moisture is present.
•Only use supplied brackets for mounting
•For PDU’s with surge protection modules, check the following 3 indicators
•Red Light: Absence of earth wire of the power supply
•Yellow Light: Live wire (L) and Neutral Wire (N) are not in the correct positions.
•Green Light: When disabled, means the failure of the lightning protection circuit.
•For pluggable equipment, the socket-outlet shall be installed near the equipment and easily accessible.
•For Pluggable or permanently connected equipment:
•Short Circuit / Overcurrent Protection: Branch circuit breaker or branch fuse, rating, number of poles, special
characteristics
•Use of this equipment in life support applications where failure of this equipment can reasonably be expected to cause the
failure of the life support equipment or to significantly affect its safety or effectiveness is not recommended. Do not use this
equipment in the presence of a flammable anesthetic mixture with air, oxygen or nitrous oxide.

OWNER’S MANUAL: EZ-PDU’S
5
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
3. NETWORK METERING
The network metered EZ-PDU’s are able to monitor the following parameters:
•Input voltage (V)
•Total load current (A)
•Total power (kW)
•Energy consumption (kWh)
•The environment inside the enclosure
Target power ranges for the EZ-PDU’s include:
•Single Phase (90VAC –240VAC) up to 63A
•Three-Phase (270VAC –400VAC) up to 32A
3.1 NETWORK METER FUNCTIONS
Function of Network Meter
Item
Function
Description
RUN
Run indicator
Flash frequency is 1 second
KWH
kWh indicator
Flash frequency depends on the load
ALM
Alarm indicator
Light is on if there is an alarm occurring
NET
Ethernet port
LAN/WAN Ethernet communication port
SER
Daisy-chain port
RS-485 daisy-chain communication port
LINK
Daisy-chain port
RS-485 daisy-chain communication port
MENU
Menu key
To view the LCD displayed information, light up the LCD background, or save the configuration,
use the MENU button as an ENTER key.
Restore to factory settings: Hold the MENU key and press the RESET button to restore.
Mute alarming: Press and hold the MENU key for 4 seconds to turn On/Off the alarm
UP
Function set key
Light up the LCD background, set the Master or Slave address cord, the maximum threshold of
voltage, current, temperature and humidity from 0 to 9
DOWN
Position
selection key
Light up the LCD background, select the address code, threshold of voltage, current, temperature
and humidity
RESET
Restart button
Restart the device
Screen
View the states
Display the power and environment status
T/H
Sensor port
Connect the external T/H sensor

OWNER’S MANUAL: EZ-PDU’S
6
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
3.2 INITIALIZATION
When powering on the EZ-PDU’s, the RUN indicator will flash and the PDU works normally after initializing the LED indicator and
TFT screen. Below are the LCD displaying content introductions from DC, single phase and three phase power sources. The user
can navigate these screens by pressing the MENU button.
Screen
1-Phase
3-Phase
DC
1
Current (A), Voltage (V),
Power (kW), Energy (kWh)
L1: Current (A), Voltage (V),
Power (kW), Energy (kWh)
Current (A), Voltage (V),
Power (kW), Energy (kWh)
2
Temp & Humidity
(from External Sensor)
L2: Current (A), Voltage (V),
Power (kW), Energy (kWh)
Temp & Humidity
(from External Sensor)
3
Baud Rate
L2: Current (A), Voltage (V),
Power (kW), Energy (kWh)
Baud Rate
4
IP Address
Temp & Humidity
(from External Sensor)
IP Address
5
Voltage and Current Threshold
Baud Rate
Voltage and Current Threshold
6
Temp & Humid Threshold
IP Address
Temp & Humid Threshold
7
N/A
L1: Voltage and Current Threshold
N/A
8
N/A
L2: Voltage and Current Threshold
N/A
9
N/A
L3: Voltage and Current Threshold
N/A
10
N/A
Temp & Humid Threshold
N/A
3.3 HARDWARE SETTINGS
Setting
Action
Address Code
To locate the address code from the LCD screen, press the DOWN key to select the master or slave
address code and press UP key to set the value from 0 to 4.
Current or Voltage
Threshold
To locate the threshold setting page, press the DOWN key to select the item, then press the UP key to
set the threshold value, the allowed maximum current is 32A and maximum voltage is 276VAC
Restore to Factory
Default
Press and hold the MENU key when powering on or Hold the MENU key to press the RESET button.
Mute the Alarm
Press and hold the MENU key for 5-6 seconds when there is an alarm to turn on/off. When the alarm
is turned on, an ON indicator will be displayed in red on the screen, When the alarm was turned off,
an OFF indicator will be displayed in red on the screen
Note: All above settings must be saved by pressing the MENU key, and the settings will take effective after the beep sound,
otherwise, the device will beep but without saving the settings.

OWNER’S MANUAL: EZ-PDU’S
7
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
3.4 DAISY CHAIN SETTINGS
Serial Daisy-chain mode
Set one EZ-PDU as the master, and the remainder as the slave units. The maximum daisy-chain is 4 PDU’s
Ethernet Daisy-chain mode
Connect the each EZ-PDU to the port from the HUB and connect the Net port from HUB to the internet. There are no PDU quantity
limits. Connect the Master net port with the computer net port, then access via IE.
3.5 SOFTWARE OVERVIEW
User can access the Network Metered EZ-PDU’s through a WEB interface, SNMP (v1) or Telnet command console.
Web Browser Access
User can access the Network Metered EZ-PDU’s via web browser through the IP address. The login window is illustrated below.
The factory default username is ‘admin’, the password is ‘admin’.

OWNER’S MANUAL: EZ-PDU’S
8
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
Device State (Home Page)
Displays the current, voltage, power and energy consumption of the Network Metered EZ-PDU.
•Select drop-down list view the power date of the Master unit or Slave units.
•Select drop-down list to view the power date of L1, L2 or L3(Three phase models only)
Threshold Setting
Set the threshold of current, voltage, temperature and humidity.
•Input Current Range:
oSingle Phase: 0-63A
oThree Phase: 0-32A
•Input Voltage Range: 170-276VAC
•Temperate range: 0-45℃
•Humidity range: 0-99%

OWNER’S MANUAL: EZ-PDU’S
9
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
Device Settings
The Device Settings are as follows:
•Device Name: Fill the device name.
•Web server port
•Work model: Revise master and slave mode, to set slave1, 2...... (Virtual Value: 1-4)
Energy Setting
Clear energy line1:Click button.
(The same operation for Line 2 and Line3 for 3phase products.)
User Settings
User can change the user name and password (the max. character length for each is 16 digits).

OWNER’S MANUAL: EZ-PDU’S
10
© 2021 ArcTiv Technologies, Ltd. ATEZPDU-MANUAL-01
Network
System IP
92.168.1.163 (factory default)
Subnet Mask
255.255.255.0
Default Gateway
192.168.1.1
DNS
202.96.128.86 (factory default)
Note: Restarting software is necessary after a modification of the network settings. Go to “Restart” section for instructions.
SNMP/Telnet
The default Get community and Set community is “public” and “private”. User can modify according to the specific application.
Fill in the trap address of SNMP management platform and the trap alarm will be sent automatically. There are 2 Trap addresses.
•Telnet settings
•Select from “Enable” or “Disable” to configure the Telnet feature, the default state is enabled.
Note: Restarting software is necessary after SNMP setting. Go to “SNMP Access (V1)” section for instructions.