3
Congratulations on your purchase of a RainSoft water treatment
system!
This Owner’s Manual is designed to assist with the operation, main-
tenance, and installation of your water treatment system. It is our
sincere hope that this manual is clear, concise, and helpful to you as
a new owner.
Questions? If you have any questions regarding the installation,
operation, or servicing of this system, please contact your local
RainSoft Dealer. Your local RainSoft Dealer is familiar with your
particular water conditions, and is able to address your concerns
promptly and efficiently.
Application Limitations
pH: The influent water must be between 6.8 and 9.0.
Iron: Third party testing conducted at 3.7 ppm of ferrous (clear
water) iron. If iron is present, the pH should be below 8.5.
Iron Bacteria: If iron bacteria are present, frequent service may
occur and the life of the system may be limited. By properly control-
ling the iron bacteria with chlorine or other approved methods for
bacterial reduction, the system will function properly.
Hydrogen Sulfide: Third party testing conducted at 1.1 ppm.
Manganese: Third party testing conducted at 1.68 ppm at an
average pH of 8.6; amounts over 1.68 ppm may gradually prevent
iron removal. For optimum manganese reduction, the pH should be
between 8.0 and 9.0. If iron is also present, the pH should be below
8.5.
Organic Matter (Tannins): The presence of organics above 2.0
ppm may hinder the operation of the system.
Chlorine: The presence of chlorine in the raw water supply should
be limited to a maximum of 1.0 ppm.
Operational Specifications
Plumbing: 3/4to 11/4
Drain Line: 1/2
Water Pressure: 20 psi–120 psi (137.89 kPa–827.37 kPa)
Actual Influent Flow Rate: (Water available from well pump,
service inlet, etc.) The actual flow rate must exceed 5 gallons per
minute. Failure to backwash the system at a rate of 5 gallons per
minute (for 150 Models) or 9 gallons per minute (for 250 Models)
will inhibit the filter’s ability to perform as designed.
Service Flow Rates: See the data chart on page 4 for maximum
service flow rates.
Operating Temperatures: 40°F–100°F (4.4°C–37.8°C)
Electrical Requirements: A properly grounded, alternating current
supply (110 VAC 60 Hz or 230 VAC 50 Hz) is required for operation.
Bypass Valve: The manually operated bypass valve enables the
system to be isolated from the water service line for maintenance,
service, and outdoor water use. It also maintains the continuity of
the water supply when the system is disconnected.
Important Note: The limitation for
Hydrogen Sulfide can vary depending on
overall water quality.
For water containing only Hydrogen
Sulfide without Iron or Manganese: Low
pH improves the conversion of Hydrogen
Sulfide by aeration. If you are using an acid
neutralizer for pH correction, we recom-
mend installing the neutralizer between
the air and filter tanks of the Oxytech
system. This will allow for the most effec-
tive conversion of Hydrogen Sulfide in the
air tank.