Antec controls PMT Series Manual de usuario

TOUCHSCREEN ROOM
PRESSURE MONITOR
PMT Series
MANUAL v115

PMT - MANUAL
1 | PMT – Manual | AntecControls.com
TABLE OF CONTENTS
INTRODUCTION ..............................................................................................................................................................................1
eneral ..........................................................................................................................................................................................1
Product Overview..........................................................................................................................................................................1
Technical Specifications ................................................................................................................................................................2
ETTIN STARTED WITH THE PMT ...............................................................................................................................................3
In the Box ......................................................................................................................................................................................3
Optional Accessories ....................................................................................................................................................................4
ELECTRICAL INSTALLATION ...........................................................................................................................................................5
Sample Wiring Diagram.................................................................................................................................................................5
Sensor Information Network (SIN) ................................................................................................................................................6
BACnet MS/TP Network ...............................................................................................................................................................7
MECHANICAL INSTALLATION ........................................................................................................................................................8
Installation and Mounting Instructions ..........................................................................................................................................8
DISPLAY NAVI ATION ...................................................................................................................................................................11
Initial Setup .................................................................................................................................................................................11
Home Screen ..............................................................................................................................................................................14
BACnet Point Monitoring ............................................................................................................................................................16
PMT Operation ............................................................................................................................................................................17
SETTIN S .......................................................................................................................................................................................18
Room Configuration ....................................................................................................................................................................19
Alarms .........................................................................................................................................................................................19
Inputs ..........................................................................................................................................................................................21
Outputs .......................................................................................................................................................................................25
Network.......................................................................................................................................................................................27
User Preferences ........................................................................................................................................................................28
Diagnostic....................................................................................................................................................................................29
About ...........................................................................................................................................................................................29
TROUBLESHOOTIN .....................................................................................................................................................................30
Replacement Parts ......................................................................................................................................................................32
Technical Support ........................................................................................................................................................................32

PMT - MANUAL
2 | PMT – Manual | AntecControls.com
INTRODUCTION
General
In this manual, you will find information regarding:
Touchscreen Room Pressure Monitor (PMT) specifications
How to install the PMT
Detailed description of PMT display navigation and
configuration
Troubleshooting information
Product Overview
The PMT is designed to provide ease of use pressure monitoring.
The PMT Home screen provides monitoring information in a
simple format displaying information including Room Status,
Pressure Mode and Isolation Mode.
Upon swiping the screen to the left, room pressure
measurement is visually available.
Some of its key features include:
Password protected menus
Setup Wizard – Walk through setup of PMT when first
powered up
LED side bars offer 180° viewing of current room status
CAUTION
This mark indicates an important point for the proper function of
the PMT. Improper installation or setup may cause unit failure.
Pay close attention to all caution points and tech tips throughout
this manual.
For local area support, please
contact your local Antec Controls
Representative
For more information visit
www.AntecControls.com

PMT - MANUAL
3 | PMT – Manual | AntecControls.com
Technical S ecifications
Environmental
(Operating) 50°F to 95°F (10°C to 35°C), 0% to 95% R.H. (non-condensing)
Environmental
(Storage) -22°F to 122°F (-30°C to 50°C), 0% to 95% R.H. (non-condensing)
Input Power 24 VAC +/- 10%, 50/60 Hz, 34 VA (external loads not included), Class 2
Inputs
1 Binary Input,
1 Binary/Analog Input,
1 SIN Input
Outputs
2 Analog Outputs (0 to 10 VDC, Max: 10 mA),
1 Dry Binary Output (Max: 24 VAC/VDC, 100 mA),
1 SIN Power Output (34 VDC, Max: 300 mA)
Display Type Capacitive Touch, 4.3 in. (109 mm) TFT/IPS, dimmable
Resolution WV A R B 480px × 272px
Communication
Protocol BACnet, SIN
BACnet
Device Type B-ASC
Communication Type MS/TP (RS-485)
Communication Speed 9600, 19200, 38400, 76800
Certification BTL
Control Priority Order 1. BACnet
2. Normal Operation
Room Pressure
Sensors (SRPS)
Environmental (Operating) 50°F to 95°F (10°C to 35°C),
0% to 95% R.H. (non-condensing)
Environmental (Storage) -22°F to 122°F (-30°C to 50°C),
0% to 95% R.H. (non-condensing)
Input Power Powered from PMT
Range +/- 0.1 in.w.c. (+/- 25 Pa)
Accuracy 3% of reading
Pressure Tubing 96in. (2438mm) long, clear, fire-rated
5/32” ID × 9/32” OD × 1/16” W
Face Plate ABS plastic (white), Stainless Steel

PMT - MANUAL
4 | PMT – Manual | AntecControls.com
GETTING STARTED WITH THE PMT
In the Box
Touchscreen Room Pressure Monitor (PMT)
Component Quantity Description
Touchscreen
Room Pressure
Monitor (PMT)
1
Single PMT
120-ohm resistor
(not pictured) 2
120-ohm resistors to be
used to terminate the
SIN and BACnet MS/TP
network
s
Room Pressure Sensor (SRPS)
Component Quantity Description
Room Pressure
Sensor
1 for single room
application
2 for dual room application
3 for triple room
application
Single SRPS
Kink Resistant Air
Tubing – 96 in.
(2.44 m)
1 for single room
application
2 for dual room application
3 for triple room
application
Air pressure tubing to
connect between
Sensor Plate and Room
Pressure Sensor
Quick Start uide 1
Document outlining
wiring and installation
instructions
Stainless Steel Sensor Plate
Component Quantity Description
Stainless Steel
Sensor Plate
2 for single room
application
4 for dual room application
6 for triple room
application
Stainless Steel plate
used as pressure sensor
inlet
Mounting
Hardware Packet
2 for single room
application
4 for dual room application
6 for triple room
application
Packet containing two
screws for j-box
mounting of Sensor
Plate
OR
ABS Sensor Plate
Component Quantity Description
ABS Sensor Plate
2 for single room
application
4 for dual room application
6 for triple room
application
ABS plate used as
pressure sensor inlet
2 for single room
application
4 for dual room application
6 for triple room
application
Packet containing two
screws and two drywall
anchors for wall
mounting of Sensor
Plate
CAUTION
Please ensure you have all components before proceeding. Inspect
components for shipping damage. Do not install any components that
appear damaged, contact your local Antec Controls Representative
for replacements.
For the latest information and videos please visit
www.AntecControls.com

PMT - MANUAL
5 | PMT – Manual | AntecControls.com
O tional Accessories
Door Switch
Door Switches can be wired into the binary input(s) to detect when the
door(s) are open.
Door Switches are available in either:
Door Contact Switch – Surface Mount
Door Contact Switch – Flush Mount

PMT - MANUAL
6 | PMT – Manual | AntecControls.com
ELECTRICAL INSTALLATION
Sam le Wiring Diagram
NOTES:
1. For typical network wiring diagrams see the Sensor Information Network (SIN) and BACnet MS/TP Network sections.
2. All wire connections to the monitor screw connection terminals must be between 16-26 AW wire.
3. All wire connections to the SRPS screw terminals must be between 12-30 AW wire.
4. Current and voltage drop should be considered when selecting wire gauge.
5. Wiring above may not reflect those required for your project. Refer to your Antec Controls Project Submittals for project
specific wiring diagrams.
Terminal Bloc Usages
Description
1 The PMT connects to the room pressure sensor through the SIN (Sensor Information Network)
terminal.
2 The PMT has native BACnet capabilities; connection is made through this BACnet MS/TP
terminal.
3
The Contact Closure allows the user to provide a binary signal on a variety of inputs.
4 The Configurable Input is typically used for a room mode switch/button; however, it has the
same capabilities as the Binary Input.
5
The Binary Input can be used to trigger setback, isolation, alarms, or cautions.
6 The PMT’s two Analog Outputs allow the user to provide a configurable 0 to 10 VDC signal on a
variety of inputs.
2 1
3 6
5
4

PMT - MANUAL
7 | PMT – Manual | AntecControls.com
Sensor Information Network (SIN)
What is the Sensor Information Networ ?
The Sensor Information Network (SIN) is a communication
protocol between the PMT and the SIN Room Pressure
Sensor (SRPS). SIN allows for digital communication
between multiple SRPSs and one single PMT touchscreen.
Networ Addressing
SIN devices will come from the factory with predefined
MAC addresses. No addressing on-site is required. Limit of
three SIN devices on one Sensor Information Network.
PMT Configuration Settings
When multiple SRPS are connected to a single PMT, each
SRPS will self address. Please ensure that each SRPS is
pinged during the Setup Wizard and the SRPS addressing
(1, 2 or 3) is recorded to each room placement. Once the
wizard is complete, the display order can be adjusted in the
Display menu, if required (see User Preferences - Display).
Physical Connection
SIN consists of a four-wire network architecture (VBUS,
VCOM, D+ and D-) using a daisy chain connection between
each device on the network segment.
Wiring Requirements
Refer to your Antec Controls Wiring Diagram Package for
typical wiring requirements and recommendations.
Ty ical SIN Wiring
NOTE: Installer must use a 120-ohm resistor at both SIN end of line terminations of the “+” and “-” terminals.
CAUTION
If the PMT is already set up and an additional SRPS is removed
or added to the SIN communication line, please restore defaults
on the PMT and re-run the Setup Wizard.

PMT - MANUAL
8 | PMT – Manual | AntecControls.com
BACnet MS/TP Network
What is BACnet?
BACnet MS/TP is a communication protocol for
communication between the PMT and the building
automation network. BACnet communication allows the
end user to verify rooms are operating as expected and
allows them to set up trends to monitor safety, and any
alarms that occur.
Each PMT will require a connection to BACnet to transmit
its information to the Building Management System (BMS).
Networ Addressing
When configuring the PMT, the user needs to assign the
unique identifying address for the room.
On any BACnet MS/TP network:
MAC Address can be between 0 and 127 and must be
unique to the MS/TP segment.
Device Instance can be between 0 and 4,194,303 and
must be unique to the facility.
Baud Rate can be 9,600, 19,200, 38,400, or 76,800 and
must match that of the Router/System Controller for
the MS/TP segment.
Typical BACnet Wiring
BACnet Points
See Touchscreen Room Pressure Monitor (PMT) Product
Submittal at AntecControls.com for BACnet Points List.
Physical Connection
BACnet consists of a three-wire network architecture.
Daisy chain the +, -, and COM connections of all devices on
the network segment. A BACnet MS/TP segment has a
limit of:
Maximum of 32 devices
Maximum length of 1050 feet (320 meters) for the
whole segment
When using shielded cable, ground the shield at one end of
the network segment only. Connect the shield of the cable
entering a device to that of the cable exiting the device.
Terminate the MS/TP network segment at each end of the
network segment by connecting a 120-ohm resistor
between the + and – terminals. Remove the termination
resistor or disable any network terminations on all devices
when adding devices to an existing network segment.
Wiring Requirements
Refer to your Antec Controls Wiring Diagram Package for
typical wiring requirements and recommendations.
NOTE: Installer must use a 120-ohm resistor at the BACnet end of line termination.
When using non-isolated power supplies (i.e. Transformer secondary
common connected to ground), do not reverse 24VAC polarity on any device,
as it is critical to the network health.
CAUTION

PMT - MANUAL
9 | PMT – Manual | AntecControls.com
MECHANICAL INSTALLATION
Installation and Mounting Instructions
Touchscreen Installation Instructions
Mount the Touchscreen Room Pressure Monitor (PMT) near the
doorway using a standard single-gang electrical box (by Others) at
a height of five feet (5 ft, 1.52 m). The recommended installation
torque is 3 in-lb (0.34 Nm) to ensure a flush mount on the wall.
Ensure LED bars are not bloc ed by other devices on the
wall.
Leave space below the PMT to ensure the set screw can be
tightened.