AIREDALE LogiCool InRak Manual de usuario

Technical Manual
LogiCool InRak™ 300mm
Chilled Water

LogiCool InRak™ IT Cooling
2
Introduction
InRak™ 300mm Technical Manual 9439563 V1.1.0_02_2017
Customer Services
Warranty, Commissioning & Maintenance
As standard, Airedale guarantees all non consumable parts only for a period of 12 months, variations tailored to suit
product and application are also available; please contact Airedale for full terms and details.
To further protect your investment in Airedale products, Airedale can provide full commissioning services,
comprehensive maintenance packages and service cover 24 hours a day, 365 days a year (UK mainland).
For a free quotation contact Airedale or your local Sales Engineer.
All Airedale products are designed in accordance with EU Directives regarding prevention of build up of water,
associated with the risk of contaminants such as Legionella.
For effective prevention of such risk it is necessary that the equipment is maintained in accordance with Airedale
recommendations.
SafeCool™
In addition to commissioning, a 24 hour, 7 days a week on-call service is available throughout the year to UK mainland
sites. This service will enable customers to contact a duty engineer outside normal working hours and receive
assistance over the telephone. The duty engineer can, if necessary, attend site, usually within 24 hours or less.
Full details will be forwarded on acceptance of the maintenance agreement.
Spares
A spares list for 1, 3 and 5 years will be supplied with every unit and is also available from our Spares department on
request.
Training
As well as our comprehensive range of products, Airedale offers a modular range of Refrigeration and Air Conditioning
Training courses, for further information please contact Airedale.
Customer Services
For information, visit us at our web site: www.airedale.com
CAUTION
Warranty cover is not a substitute for maintenance. Warranty cover is conditional to maintenance
being carried out in accordance with the recommendations provided during the warranty period.
Failure to have the maintenance procedures carried out will invalidate the warranty and any
liabilities by Airedale International Air Conditioning Ltd.

IT Cooling
LogiCool InRak™
3
Introduction
InRak™ 300mm Technical Manual 9439563 V1.1.0_02_2017
Health and Safety
IMPORTANT
The information contained in this manual is critical to the correct operation and maintenance of the unit and should be
read by all persons responsible for the installation, commissioning and maintenance of this Airedale unit.
Safety
The equipment has been designed and manufactured to meet international safety standards but, like any mechanical/
electrical equipment, care must be taken if you are to obtain the best results.
Electrical installation commissioning and maintenance work on this equipment should be undertaken by competent and
trained personnel in accordance with local relevant standards and codes of practice.
A full hazard data sheet in accordance with COSHH regulations is available should this be required.
Personal Protective Equipment
Airedale recommends that personal protective equipment is used whilst installing, maintaining and commissioning
equipment.
Electrical Bonding
It is important that the components attached to the server rack are electrically bonded to earth correctly.
It is recommended that a mechanical earth strap is used at the following locations:
• Doors
• LogiCool InRak
• LogiCool InRak Chilled Water Coil
• Dual Power Supplies
Manual Handling
Some operations when servicing or maintaining the unit may require additional assistance with regard to manual
handling. This requirement is down to the discretion of the engineer.
Remember do not perform a lift that exceeds your ability.
CAUTION
When working with any air conditioning units ensure that the electrical isolator is switched off prior
to servicing or repair work and that there is no power to any part of the equipment.
Also ensure that there are no other power feeds to the unit such as re alarm circuits, BMS circuits
etc.

LogiCool InRak™ IT Cooling
4
Introduction
InRak™ 300mm Technical Manual 9439563 V1.1.0_02_2017
Environmental Considerations
Airedale Ltd endeavours to ensure that the information in this document is correct and fairly stated, but none of the
statements are to be relied upon as a statement or representation of fact. Airedale Ltd does not accept liability for any
error or omission, or for any reliance placed on the information contained in this document. The development of Airedale
products and services is continuous and the information in this document may not be up to date. It is important to check
the current position with Airedale Ltd at the address stated. This document is not part of a contract or licence unless
expressly agreed. No part of this document may be reproduced or transmitted in any form or by any means, electronic
or mechanical, including photocopying, recording, or information storage and retrieval systems, for any purpose other
than the purchaser’s personal use, without the express written permission of Airedale Ltd.
© 2017 Airedale International Air Conditioning Limited. All rights reserved. Printed in the UK.
Freeze Protection
Airedale recommends the following actions to help protect the unit during low temperature operation. This also includes
the units subject to low ambient temperatures. The Logicool InRak must have a minimum of 20% glycol as standard.
Units with supply water temperatures below +5°C
Glycol is recommended when a supply water temperature of +5°C or below is required or when static water can be
exposed to freezing temperatures.
Units subject to ambient temperatures lower than 0°C
Glycol of an appropriate concentration (1) must be used within the system to ensure adequate freeze protection.
Please ensure that the concentration is capable of protection to at least 3°C lower than ambient.
Water/glycol solution should be constantly circulated through all waterside pipework and coils to avoid static water from
freezing.
Ensure that pumps are started and running even during shut down periods, when the ambient is within 3°C of the
solution freeze point (1) (i.e. if the solution freezes at 0°C, the pump must be operating at 3°C ambient).
Additional trace heating is provided for interconnecting pipework.
(1) Refer to your glycol supplier for details.
Environmental Policy
It is our policy to:
• Take a proactive approach to resolve environmental issues and ensure compliance with regulatory requirements.
• Train personnel in sound environmental practices.
• Pursue opportunities to conserve resources, prevent pollution and eliminate waste.
• Manufacture products in a responsible manner with minimum impact on the environment.
• Reduce our use of chemicals and minimise their release to the environment.
• Measure, control and verify environmental performance through internal and external audits.
• Continually improve our environmental performance.
CE Directive
Airedale certify that the equipment detailed in this manual conforms with the following EC Directives:
Electromagnetic Compatibility Directive (EMC) 2014/30/EU
Low Voltage Directive (LVD) 2014/35/EU
Machinery Directive (MD) 89/392/EEC version 2006/42/EC
Pressure Equipment Directive (PED) 2014/68/EU
To comply with these directives appropriate national & harmonised standards have been applied. These are listed on the
Declaration of Conformity, supplied with each product.
Maximum and Minimum Operation Temperature (TS) and Pressure (PS)
Operating Temperature (TS), TS = Min -20°C to Max 40°C *
Maximum Operating Pressure (PS) PS = High Side 10 Barg
*Based upon the maximum machine running temperature

Contents
Customer Services 2
Health and Safety 3
Manual Handling 3
Environmental Considerations 4
Freeze Protection 4
Environmental Policy 4
Speciers Guide 6
Nomenclature 6
Introduction 6
Unit Overview 7
General 9
Airow 11
Electrical 13
Controls 15
Lon BMS Connection 17
Technical Data - Chilled Water 18
Operating Limits 18
Performance Data 19
Mechanical Data 20
Electrical Data 21
Sound Data 22
Unit Pressure Drop 23
Coil Pressure Drop Curves 23
Installation 24
Dimensions 24
Packaging 25
Clearance 27
Levelling 28
Electrical Services Incoming Cabling 31
Interconnecting Wiring 33
Commissioning 34
Maintenance 35
General Inspections 36
Controls 37
Electrical Inspection 38
Waterside 39
System 40
Troubleshooting 41
Alarms 42
Alarm Menu Display 42
After Sales 43
Warranty 43
IT Cooling
LogiCool InRak™
5
Introduction
InRak™ 300mm Technical Manual 9439563 V1.1.0_02_2017

Speciers Guide
Nomenclature
Introduction
The LogiCool InRak is an efcient in-row IT cooling solution for data centre applications. The InRak delivers complete
condence, with redundancy features such as dual power supplies. It is extremely efcient, offering the latest fan
technology coupled with sophisticated controls logic designed to optimise operation.
The InRak delivers even greater efciency when combined with Airedale’s latest free cooling chillers.
Providing industry-leading cooling for its footprint, the InRak offers the ultimate in scalable solutions for the modern data
centre. The InRak is designed to t in between industry standard server racks and offer “plug and play“ connectivity.
Construction
The cabinet shall be manufactured with galvanised sheet steel to provide a smooth aesthetically pleasing nish. The
galvanised sheet steel panels shall be coated with an epoxy baked powder paint to provide a durable nish.
Standard unit colours shall be Black Grey (RAL 7021) or Light Grey (RAL 7035).
Standard Features
• Chilled water cooling
• Variable capacity
• 300mm wide case size
• Multi-cabinet cooling solution
• 50Hz/60Hz power supply
• Dew point control
• Top or bottom service connections
• Aisle differential pressure control
Example: LIR 30 42U - C0 40 - 7
LIR
30
42U Unit height in U
-Separator
C0 Chilled water cooling, single circuit
Min
Max
-Separator
7230V / 1PH / N / 50H
z
8220V / 1PH / N / 60Hz
LogiCool InRak
Case width in centimetres
Nominal cooling capacity in kW
LogiCool InRak™ IT Cooling
6
Introduction
InRak™ 300mm Technical Manual 9439563 V1.1.0_02_2017

Unit Overview
Standard Front Door Features
• Discharge Grille
• Removable Access Panel
• Secure Door Lock
Standard Construction Features
• Levelling Feet
• Castors
• Anti-Recirculation Brush Seal
• Side Access Panels
Standard Control Features
• Microprocessor Control
• Graphical Display
• Unit Status LED
• Dew Point Control
Optional Control Features
• Touch Screen Colour Display
• Filter Change Monitoring
• Aisle Pressure Management
• Constant Air Volume Control
• Water Detection
• Fire / Smoke Detection
IT Cooling
LogiCool InRak™
7
Introduction
InRak™ 300mm Technical Manual 9439563 V1.1.0_02_2017

Unit Overview
Standard Rear Door Features
• Secure Door Lock
• Return Air Grille
Optional Rear Door Features
• G4 Return Door Air Filters
Standard Electrical Components
• Electrical Switch Gear
• Controller UPS Backup
Optional Electrical Components
• Condensate Pump
• Energy Manager
• Phase Rotation Monitoring
• IEC 60309 Plug and Socket
Standard Chilled Water Features
• Efcient Chilled Water Coil
• Bleed / Drain Valves
• Modulating Control Valve
Optional Chilled Water Features
• 3 Way Chilled Water Valve
• 2 Way Chilled Water Valve
• 2 Way PICV Valve
• Bypass Regulating Valve
LogiCool InRak™ IT Cooling
8
Introduction
InRak™ 300mm Technical Manual 9439563 V1.1.0_02_2017

General
System Conguration
General
Features CW
Hydrophilic Fin Chilled Water Coil ●
Top Service Connections* ○
Bottom Service Connections* ○
Axial Fan Door ●
2 Way Chilled Water Regulating Valve ●
3 Way Chilled Water Regulating Valve ○
2 Way PICV Valve ○
Condensate Pump** ○
Brazed Pipework Connection ●
Threaded Pipework Connection ○
Flexible Hose Connection 1.5m or 3m ○
Flexible Hose Termination Male/Female ○
●Standard Features ○Optional Features –Feature Not Available
* At least one is selected at time of order
** required for top entry systems
Compact Cooling Coil
3/8” plain tube cooling coil with and hydrophilic ns.
300mm Case Size
300mm case width shall offer high cooling capacity for space-critical applications.
Top and Bottom Service Connections
The unit shall offer top and bottom service connections for maximum accessibility.
Axial Fan Door
The fan doors shall have a hex-punch pattern and attach to the frame with hinges.
IT Cooling
LogiCool InRak™
9
Introduction
InRak™ 300mm Technical Manual 9439563 V1.1.0_02_2017

2 Way Chilled Water Regulating Valve
The chilled water valve has an indication of ow on the stem. The
actuator is securely attached to the top of the valve so that when
there is a demand for cooling the valve opens allowing water to ow
through the coil. No demand, the water is shut off allowing no water to
enter the coil (0 VDC no demand, 10 VDC 100% demand).
3 Way Chilled Water Regulating Valve
The chilled water valve has an indication of ow on the stem. The
actuator is securely attached to the top of the valve so that when
there is a demand for cooling the valve opens allowing water to ow
through the coil. No demand, the water goes through the bypass (0
VDC no demand, 10 VDC 100% demand).
2 Way PICV Valve
2-way pressure independent control valves, internally mounted 0-10V
DC PICV valves shall be used to compensate for pressure variations,
performing a continual balancing function to maintain system
performance at varying loads.
Bypass Regulating Valve
A bypass regulating valve shall be tted in the bypass leg of the
system to enable constant ow when there is no cooling demand.
This simulates the coil pressure drop ensuring that the water ow rate
does not change irrespective of amount of ow through the chilled
water coil.
This enables ow through each cooling module without the need for a
Cooling Distribution unit (CDU).
Condensate Pumps
The InRak condensate pump shall be a cold water type (cooling only).
The pump shall be able to pump water 10l/hr @15m maximum head.
Pipework Termination
Pipework shall be terminated in either:
• Brazed Pipework
• Threaded Pipework Connection (BSP)
• Flexible Hose Connection
Flexible Hose Connection
A Flexible Hose connection shall be tted to the unit. Length of 1.5 and 3m shall be avaliable. Hose ends can be either
Male or Female.
LogiCool InRak™ IT Cooling
10
Introduction