AirCycler g2-k Guía de configuración

AirCycler® g2-k
Training Guide
VENTILATION MADE BREEZY!™
a breeze to install • a breeze to use
SIMPLE VENTILATION SOLUTIONS

TABLE OF CONTENTS
AirCycler® g2-k Introduction
Safety Considerations
Installation Considerations
AirCycler® g2 Controller Location
Damper Location & Damper Installation
Choose a Fresh Air Location
Battery (Model CR1220)
AirCycler® g2-k Wiring
FanConnect™ Switch Wiring (Optional)
1.0 Theory of Operation
1.1 Operation Details
1.2 Operation Examples
2.0 AirCycler® g2 Operation
2.1 Reading the AirCycler® g2
2.2 Normal Operation Display
2.3 Entering Setup Mode
3.0 Setup Options
4.0 Calculated Flow Set Up
4.1 Setting Measured Supply Air Flow
4.2 Setting Measured Exhaust Air Flow
4.3 Setting Code Required Constant Air Flow
4.4 Setting Optional Mixing Time
4.5 Setting Operation Hours
4.6 Setting Exhaust Fan Delay Time
5.0 Calculated Time Set Up
5.1 Setting Number of Minutes Per Hour of Supplied Air Flow
5.2 Setting Minutes of Exhaust Fan Run Time Required
5.3 Setting Optional Mixing Time
5.4 Setting Operation Hours
5.5 Setting Current Time
5.6 Setting Exhaust Fan Delay Time
6.0 Viewing Current Status & Settings
6.0 Currrent Status
6.1 Current Settings
6.2 Setting Current Time
6.3 Reset to Default Values
7.0 Installation Testing Guide
Appendix A: Troubleshooting & Tips
Appendix B: ASHRAE 62.2 Reference Chart

3AC DOC 8.5
REV 7/2020
AIRCYCLER® G2-K INTRODUCTION
The AirCycler® g2-k Whole House Mechanical Ventilation System includes the AirCycler® g2 Furnace Fan Timer,
FanConnect™ Bath/Fan Light Switch with remote fan control, and a motorized fresh air damper.
The AirCycler® g2 is a furnace fan timer and ventilation controller with outputs for operating a motorized fresh air
damper and the FanConnect™ exhaust fan switch*. This product provides whole house supply ventilation through cen-
tral furnace fan integration as well as whole house exhaust ventilation.
How does it work?
The AirCycler® g2-k System is integrated with the home’s HVAC system. When the home’s furnace fan is turned on
by the thermostat to provide heating or cooling, the AirCycler® g2 controller opens the motorized damper to let in
a measured amount of fresh air. The fresh air is ltered by the return plenum lter and is then distributed uniformly
throughout the home through the existing ductwork. Once the ventilation requirements are met, the damper is closed
to prevent over-ventilation.
By running the ventilation system at the same time as the home’s regular heating and cooling cycles, the AirCycler®
g2-k System saves on additional utility costs.
Should regular heating and cooling cycles not run long enough to meet the desired or required ventilation, the
AirCycler® g2 can turn on the smaller and more economical bathroom exhaust fan (or other exhaust fan) through the
optional FanConnect™ Switch. With no need to run the large central fan to provide additional ventilation, homeowner
complaints of cold air or noisy operation are eliminated and eciency is drastically improved.

4AC DOC 8.5
REV 7/2020
SAFETY CONSIDERATIONS
Read and follow manufacturer’s instructions carefully. Follow all local electrical codes during installation. All wiring
must conform to local and national electrical codes. Improper wiring or installation may result in personal injury or
product and property damage.
INSTALLATION CONSIDERATIONS
The AirCycler® g2 requires 24VAC (R and C terminals) to be connected for proper operation. The controller will not
operate without these two connections.
The wires (R, C, & W ) from the air handler to the thermostat can run parallel with the wiring from the AirCycler®
g2 to the air handler. The fan wire (G) must be interrupted by the AirCycler® g2. Some thermostats do not require a
common (C) connection. The AirCycler® g2 requires this for power, which must be wired to the furnace.
AIRCYCLER® g2 CONTROLLER LOCATION
The AirCycler® g2 controller can be installed near the thermostat or out of view on/near the air handler unit. See the
wiring diagram on page 4.
Warning: Before installing the AirCycler®, turn o all power to the furnace. There may be more than one power to disconnect.
Electrical shock can cause injury or death.
DAMPER LOCATION
The fresh air damper can be located anywhere in the inlet duct. Minimize the length of the inlet duct to improve air
ow and improve system eciency. It is recommended that the damper be as close to the return air plenum and the
AirCycler® g2 controller as possible, and the inlet duct connect to the return plenum upstream of the system lter, and
down- stream of any duct mounted sensors.
DAMPER INSTALLATION
The damper may be installed in any position. It is recommended to install it with the motor at the12 o’clock position if
mounted horizontally. Air may ow through in either direction, although it is recommended to install with the crimped
end as the outlet. Use care to avoid distorting the damper housing and provide adequate support. Upon system start up
be sure to set damper power switch to UP or AUTOMATIC position.
CHOOSE A FRESH AIR LOCATION
ASHRAE recommends that the fresh air intake be located at least 10 ft. from any source of pollutants, such as auto
exhaust, dryer exhaust, exhaust from any fuel-burning appliances, etc. Avoid installation near odor sources such as
garbage bins or barbecue grills. A minimum of 3 ft. above ground is recommended to avoiding ingress of leaf litter,
grass clippings, etc. Do not use a crawl space, basement, or attic as a source of intake air. Always be sure to comply with
local building codes and requirements regarding fresh air inlets.
BATTERY (MODEL CR1220)
The AirCycler® g2 is equipped with a real time battery backed-up clock for use with the Operation Hours setting ONLY.
If not setting the hours of operation, the included battery is not required. All other settings are saved in nonvolatile
memory.

5AC DOC 8.5
REV 7/2020
RECORD ALL SETTINGS ON THE INSTALL STICKER PROVIDED. LIMITED
WARRANTY WILL BE VOID IF THE STICKER IS NOT PRESENT.

6AC DOC 8.5
REV 7/2020
AIRCYCLER® G2-K WIRING
Class 2
conductors
KEY
R - 24VAC Power
C - Common
W - Heating
Gt - Fan From Thermostat
Gf - Fan To Furnace
V - Vent
Ex - Exhaust Fan
Vnc - Normal Closed Vent
(To power spring-return
dampers that are
normally open)

7AC DOC 8.5
REV 7/2020
3191003
CONFORMS TO UL
STD. 917
FANCONNECT™ SWITCH WIRING (OPTIONAL)
INTRODUCTION
Power for the g2 controller, damper and FanConnect™
switch comes from the 24VAC supply in the furnace.
The damper draws only 35mA during the 15 seconds it
takes to open or close.
The relay in the FanConnect™ switch draws 100mA when
the controller is activating the bath fan.
All can be wired with standard 18-22awg 600V thermostat
wire.
DAMPER
FURNACE
THERMOSTAT
Y R W G
Y R C Wt Gt Gf Wf V
AirCycler G2
Y R C W G
FanConnect switch
FanConnect
TM
Class 2
conductors
WIRING
The switch requires an always hot
110VAC feed. (Black wire & White
neutral wire)
The Blue 110VAC switch leg (load)
powers the light circuit. It is a simple
mechanical contact within the toggle
switch. It can handle up to 450 Watts.
The Red 110VAC switch leg (load)
powers the fan. This is also a mechanical
contact within the internal relay. It can
handle up to 150 Watts. Works ne with
DC fans.
INSIDE THE FANCONNECT™ SWITCH
Inside the FanConnect™ switch is a
24VAC relay to control the 110VAC bath
fan.
Anytime the light switch is turned on,
the fan circuit is energized supplying
power to the fan.
The AirCycler® g2 controller can:
• Read when the bath fan is on and
track that time.
• Turn fan on for a delay time after
bathroom is used.
• Turn fan on for a programmed
amount of time every hour to meet
ventilation requirements.
Blue (light)
FanConnect Switch
Any light
up to 450w
Any fan
up to 150w
24VAC @100mA
White (Neutral)
Black (110VAC - Hot)
Internal Relay
Red (fan)
Clock-Operated Switches (UL 917 5th Ed., Rev. October 7,
2009) & Clock-Operated Switches (CAN/CSA C22.2 No. 177-92,
Rev. October, 2000)

8AC DOC 8.5
REV 7/2020
ONE HOUR VENTILATION (MINUTES)
VENTILATION REQUIREMENTS = 30 CFM CONTINUOUS OR 1,800 CF/HR
1.0 THEORY OF OPERATION
15 30 45 60
0
20 MINUTES OF
HEATING/COOLING
CENTRAL FAN
20 MIN x 90 CFM
= 1,800 CF
NORMAL CENTRAL FAN OPERATION ONLY
= NORMAL OPERATION = OCCUPANT ACTIVITY/AIRCYCLER® G2 FORCED EXHAUST
DAMPER
OPEN
DAMPER
CLOSED
VENTILATION
REQUIREMENT
COMPLETE
Enough ventilation took place during normal heating/cooling cycles to meet ventilation requirements for the hour.
No need for additional ventilation forced by AirCycler® g2.
1.1 OPERATION DETAILS
The AirCycler® g2 Furnace Fan Timer is integrated with the home’s central furnace fan so that any time the central
fan is turned on by the thermostat to provide heating or cooling, the AirCycler® g2 opens the motorized damper to
let in a measured amount of fresh air. The fresh air is then distributed uniformly throughout the home through the
existing ductwork.
When ventilation requirements are met, the damper is closed to prevent over-ventilation.
Should regular heating and cooling cycles not run long enough to meet the desired or required ventilation, the
AirCycler® g2 can turn on the smaller and more economical bathroom exhaust fan (or other exhaust fan) through the
optional FanConnect™ Switch.
With no need to run the large central fan to provide additional ventilation, homeowner complaints of cold air or noisy
operation are eliminated and eciency is drastically improved.
1.2 OPERATION EXAMPLES

9AC DOC 8.5
REV 7/2020
15 30 45 60
0
15 MINUTES OF
HEATING/COOLING
CENTRAL FAN EXHAUST FAN
15 MIN x 90 CFM
= 1,350 CF
7.5 MIN x 60 CFM = 450 CF
450 CF + 1,350 CF = 1,800 CF
DAMPER
OPEN
DAMPER
CLOSED DAMPER
OPEN
DAMPER
CLOSED
VENTILATION
REQUIREMENT
COMPLETE
FORCED ON
BY G2 VIA
FANCONNECT
FOR 7.5 MIN
NORMAL CENTRAL FAN OPERATION + AIRCYCLER® G2 FORCED EXHAUST
= NORMAL OPERATION = OCCUPANT ACTIVITY/AIRCYCLER® G2 FORCED EXHAUST
After regular heating/cooling cycles, ventilation requirements for the hour were not met. At the end of the hour the
AirCycler® g2 forced on the bathroom exhaust fan, via the FanConnect™ switch, to reach required ventilation.
ONE HOUR VENTILATION (MINUTES)
VENTILATION REQUIREMENTS = 30 CFM CONTINUOUS OR 1,800 CF/HR
15 30 45 60
0
10 MINUTES OF
HEATING/COOLING
CENTRAL FAN EXHAUST FAN
10 MIN x 90 CFM
= 900 CF
15 MIN x 60 CFM = 900 CF
NORMAL CENTRAL FAN OPERATION + OCCUPANT EXHAUST USE
= NORMAL OPERATION = OCCUPANT ACTIVITY/AIRCYCLER® G2 FORCED EXHAUST
DAMPER
OPEN
DAMPER
CLOSED
DAMPER
OPEN
DAMPER
CLOSED
900 CF + 900 CF = 1,800 CF
VENTILATION
REQUIREMENT
COMPLETE
15 MIN OF
BATHROOM USE
(MANUAL USE
OF FANCONNECT
SWITCH)
After regular heating/cooling cycles and manual occupant use of bathroom exhaust fan, ventilation requirements for the
hour were met. No need for additional ventilation forced by AirCycler® g2.
1.2 OPERATION EXAMPLES CONT’D

10 AC DOC 8.5
REV 7/2020
1.2 OPERATION EXAMPLES CONT’D
ONE HOUR VENTILATION (MINUTES)
VENTILATION REQUIREMENTS = 30 CFM CONTINUOUS OR 1,800 CF/HR
15 30 45 60
0
10 MINUTES OF
HEATING/COOLING
FORCED ON
BY G2 VIA
FANCONNECT
FOR 5 MIN
CENTRAL FAN EXHAUST FAN
EXHAUST FAN
5 MIN OF
BATHROOM USE
(MANUAL USE
OF FANCONNECT
SWITCH)
10 MIN x 90 CFM
= 900 CF
(5 MIN + 5 MIN) x 60 CFM
= 600 CF
5 MIN x 60 CFM
= 300 CF
NORMAL CENTRAL FAN OPERATION + OCCUPANT EXHAUST USE + AIRCYCLER® G2 FORCED EXHAUST
= NORMAL OPERATION = OCCUPANT ACTIVITY/AIRCYCLER® G2 FORCED EXHAUST
DAMPER
OPEN
DAMPER
CLOSED DAMPER
CLOSED
DAMPER
OPEN
DAMPER
OPEN
5 MIN
DELAY
900 CF + 600 CF
+ 300 CF = 1,800 CF
VENTILATION
REQUIREMENT
COMPLETE
After regular heating/cooling cycles and manual occupant use of bathroom exhaust fan (including 5 minute delay), there was not enough
ventilation to meet requirements for the hour. At the end of the hour the AirCycler® g2 forced on the bathroom exhaust fan, via the
FanConnect™ switch, to reach required ventilation.
Otros manuales para g2-k
2
Tabla de contenidos
Otros manuales de Admirador de AirCycler



















