10
- Pass the transport pipes through the holes in the base frame.
- Secure the transport pipes with screws.
- Pass the chain or rope to the end of the pipe.
- Prevent damage to the device from chains or ropes with wooden stick as shown. (Fig.4)
- Use a wooden stick to prevent the chain or ropes from damaging the device.
- Provide a symmetrical load distribution before lifting the device.
- Lift the device slowly.
Risk of personal injury and equipment damage!
The packages may have an eccentric center of gravity. If the packages are lifted incorrectly they can be dropped. Falling or
overturned packages may cause serious injury.
While the packages are being lifted, the crane hook should be located above the center of gravity of the packages.
1.7 Intended use
EVO-R units are highly energy efficient, fully automated, quiet and plug-and-play air handling units. EVO-R devices are
designed in 9 different models to correspond the need of up to 15000 m3/ h air flow. There is an ePM1 55% class filter on the
outdoor air side and an ePM10 50% class filter on the exhaust side as standard.
EVO-R devices are designed with energy efficient, low sound pressure radiating and low power consumption plug fans. Plug
fans with EC motors can be driven with 3 fixed speeds (reduced-normal-boost) or steplessly with the help of an air quality
sensor thanks to build in smart control system.
The EVO-R units are equipped with rotary heat exchanger. More than 80 % of the extract air heat is transferred to the outdoor
air depending on working conditions. The supply air is led by the duct system to the primary (supply air needing) areas. The
used air is extracted from the secondary areas. It flows back through the ducting to the ventilation unit, transfers the heat and is
discharged by the exhaust air duct to the atmosphere.
The AERA EVO-R units are only intended for handling of air and performing the following jobs:
- filtering normally polluted air
- air heating and/or cooling
- heat recovery
- or combination of the above-mentioned functions.
Proper use also includes observance of the operation manual and instructions from the manufacturer of the individual
components, as well as the inspection and maintenance intervals stipulated by AERA.
EVO-R devices application limits can be seen below.
Ambient Temperature with
e-box heater (°C)
ODA/ETA Air Temperature (°C)
The standard equipment permits the installation and the application in frost-free rooms > 0 °C. If the
device is used at < 0 °C, it is necessary to use a heater in the device electronic box. (optionally)
Corrosion level of the sheet metal is C4 according to ISO 12944. The unit is durable under these
conditions.
Interior: Chemical manufacturers, swimming baths and ship- and boatyards by the sea.
Exterior: Industrial areas and coastal areas with moderate salt impact.