The picture below shows the terminal block positions for
each switch input.
Install cables suitable for the application and degree of fire
protection required. These circuits are SELV type.
If additional knockouts are required, use the deeper back
box (Mxm-020) or use the Termination Enclosures (Mxm-
028 or Mxm-029) as appropriate.
Figure 6
All electrical wiring installation work should be
carried out in accordance with the code of
practice applicable in the country of installation.
To maintain electrical integrity of the SELV
wiring on the input lines all SELV wiring should
be segregated from the LV mains wiring and be
wired using cable with insulation suitable for the
application.
To minimise the effects of EMC interference all
data wiring circuits should be wired with a
twisted pair of conductors with a cross sectional
area suitable for the loading conditions.
In areas where cabling may come into contact
with high frequency interference, such as
portable radio transceivers etc. the input wiring
cable should be of a twisted pair construction
within an overall screen. The screen should be
terminated to one of the dedicated earth studs
available in the panel (refer to panel manual for
positions).
NB: Minimum / Maximum cable size for all
connections is limited to 0.35mm² / 2.5mm² (22-
14AWG).
Click on the circuit icon
Adjust the “Point Details” as required. The input action, delay, etc. can then be defined.
For further information on PC programming, see document reference 680-021.