8
Relay Group
Name Address Range Explain Initial Read/
Write Note
ST_BAND 0x0014 0~9999 Start band 0 R/W
ST_DELAY 0x0015 0~5999 Delay on (x0.1s) 0 R/W
RELAY1_SP 0x0016 -19999~30000 First relay action function 10000 R/W
RELAY1_MODE 0x0017 0~4
First relay action mode
0: OFF 1: LO 2: HI
3: LO.HOLD 4: HI.HOLD
2 R/W
RELAY1_HY 0x0018 0~9999 First relay hysteresis 0 R/W
RELAY1_RD 0x0019 0~5999 First relay delay on (x0.1s) 0 R/W
RELAY1_FD 0x001A 0~5999 First relay delay off(x0.1s) 0 R/W
RELAY2_SP 0x001B -19999~30000 Secondary relay action function 20000 R/W
RELAY2_MODE 0x001C 0~4
Secondary relay action mode
0: OFF 1: LO 2: HI
3: LO.HOLD 4: HI.HOLD
2 R/W
RELAY2_HY 0x001D 0~9999 Secondary relay hysteresis 0 R/W
RELAY2_RD 0x001E 0~5999 Secondary relay delay on (x0.1s) 0 R/W
RELAY2_FD 0x001F 0~5999 Secondary relay delay off(x0.1s) 0 R/W
Analogue Output Group
Name Address Range Explain Initial Read/
Write Note
AO1.TYP 0x0024 0~5
AO1 Analogue output range
0: 0-10V 1: 0-5V 2: 1-5V
3: 0-10mA 4: 0-20mA 5: 4-20mA
0 R/W
AO1.LS 0x0025 -19999~30000 AO1 Output low scale 0 R/W
AO1.HS 0x0026 -19999~30000 AO1 Output high scale 30000 R/W
AO1_ZERO 0x0027 -19999~32767 AO1 zero adjustment 0 R/W
AO1_SPAN 0x0028 -19999~32767 AO1 span adjustment 0 R/W
AO1.CLR 0x0029 0~3
AO1 Clear zero and span adjustment
0: NONE 1: ZERO
2: SPAN 3: BOTH (Clear all)
0 R/W
AO1.H.LMT 0x002A 0~11000 AO1 Output high limit (x0.01%) 11000 R/W
AO1.L.LMT 0x002B 0~5000 AO1 Output low limit (x0.01%) 0 R/W
AO2.TYP 0x002C 0~5
AO2 Analogue output range
0: 0-10V 1: 0-5V 2: 1-5V
3: 0-10mA 4: 0-20mA 5: 4-20mA
0 R/W
AO2.LS 0x002D -19999~30000 AO2 Output low scale 0 R/W
AO2.HS 0x002E -19999~30000 AO2 Output high scale 30000 R/W
AO2_ZERO 0x002F -19999~32767 AO2 zero adjustment 0 R/W
AO2_SPAN 0x0030 -19999~32767 AO2 span adjustment 0 R/W
AO2.CLR 0x0031 0~3
AO2 Clear zero and span adjustment
0: NONE 1: ZERO
2: SPAN 3: BOTH (Clear all)
0 R/W
AO2.H.LMT 0x003A 0~11000 AO2 Output high limit (x0.01%) 11000 R/W
AO2.L.LMT 0x003B 0~5000 AO2 Output low limit (x0.01%) 0 R/W