Acuity Controls | 900 Northrop Road,Wallingford, CT 06492 PHONE: (800)-727-7483 nLightcontrols.com ©2015 Acuity Brands Lighting, Inc. All rights reserved. 01/26/15 2 of 2
nCM xx RJB
FAMILY INSTRUCTIONS
WARRANTY
5-year limited warranty. Full warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Note: Specications subject to change without notice. Actual performance may dier as a result of end-user environment and application.
The following instructions are for mounting sensor directly to a ceiling tile or
sheetrock surface. Sensor’s mounting holes also align with standard round xture or
single gang handy box (screws not provided).
1. Using template included with unit, mark spots on ceiling tile/sheetrock for cable
hole and mounting anchors/screws
2. Drill 1/2”hole through ceiling surface at location indicated on template
3. Insert provided anchors into ceiling surface at locations indicated on template
4. Remove provided RJ-45 splitter from sensor’s attached CAT5e cable and
thread cable (and low voltage wires if -AR option included) through hole from
underside
5. Mount sensor to anchors using two screws provided
6. Reattach RJ45 splitter device (model CAT5 Y) above ceiling to cable from sensor
(see diagram on right)
7. Interconnect CAT-5e cables to/from rest of nLight zone to RJ45 splitter
8. Once power is received via CAT-5e connection, all devices in zone will
automatically begin functioning together according to each device’s defaults
9. Install decorative sensor lid by rotating clockwise
10. Refer to included instruction card for default settings and directions on push-
button programming.
INSTALLATION / WIRING
Sheet#: TNG-139-001
CAT-5e
BRN
BRN
T-5e Splitter
CAT-5e CAT-5e
- AR option
(contact closure)
to/from nLight
Zone
• To reduce the risk of death, personal injury or property damage from re, electric shock, falling parts, cuts/abrasions, and other
hazards please read all warnings and instructions included with and on the xture box and all xture labels.
• Before installing, servicing, or performing routine maintenance upon this equipment, follow these general precautions.
• Installation and service should be performed by a qualied licensed electrician.
• Maintenance should be performed by qualied person(s) familiar with the products’ construction and operation and any haz-
ards involved. Regular maintenance programs are recommended.
READ AND FOLLOW ALL SAFETY INSTRUCTIONS!
SAVE THESE INSTRUCTIONS AND DELIVER TO OWNER AFTER INSTALLATION
• DO NOT INSTALL DAMAGED PRODUCT! This product has been properly packed so that no parts should have been damaged
during transit. Inspect to conrm. Any part damaged or broken during or after assembly should be replaced.
CAUTION: RISK OF PRODUCT DAMAGE
√ Electrostatic Discharge (ESD): ESD can damage product(s).
Personal grounding equipment should be worn
during all installation or servicing of the unit.
√ Do not touch individual electrical components, as this can cause
ESD and aect product performance.
√ Do not stretch or use cable sets that are too short or are of insuf-
cient length.
√ Do not tamper with contacts.
√ Do not modify the product.
√ Do not change or alter internal wiring or installation circuitry.
√ Do not use product for anything other than its intended use.
WARNING - RISK OF BURN or FIRE
√ Do not exceed maximum wattage, ratings, or published operation conditions
of product.
√ Do not overload.
√ Follow all manufacturer’s warnings, recommendations and restrictions to
ensure proper operation of product.
CAUTION - RISK OF INJURY
√ Wear gloves and safety glasses at all times when installing, servicing or performing
maintenance.
WARNING - RISK OF ELECTRIC SHOCK
√ Disconnect or turn o power before installation or servicing.
√ Verify that supply voltage is correct by comparing it with the product
information.
√ Make all electrical and grounded connections in accordance with the National
Electrical Code (NEC) and any applicable local code requirements.
√ All wiring connections should be capped with UL approved recognized wire
connectors.
√ All unused connector openings must be capped.
Note: T568B pin/pair assignment is recommended for all CAT-5e cables. Sensor
power is provided via a CAT-5e connection to an nLight power pack/supply, nLight
enabled digital luminaire, or nLight Bridge.