•Field-pluggable microBlox® input module allows you to change an input type
on this carrier in the field. Modules are over-molded and RoHS compliant,
and offer superior shock, moisture, and dust protection.
•Software Configuration via wired USB to a Windows based personal computer
or tablet running Windows software, or wired USB OTG (On-The-Go) to an
Android smartphone or tablet using our Agility Configuration App. Software
for USB Configuration and the Agility app is free (no other software required).
•Separate isolated voltage and current outputs at each splitter output channel
support ±10V, ±5V, 0-10V, 0-5V, or 0-20mA and 4-20mA ranges. A third
isolated AUX/host voltage output is sourced from the microBlox® module.
•Input range and output ranges are adjustable, input and outputs can be
scaled independently and the input may even be scaled differently for each
output.
•Normal or Reverse Acting splitter outputs.
•Variable Digital Input Filter adjustment.
•Designed and manufactured for High Quality/High Reliability with AS9100
(Aerospace Quality)/ISO9001.
•Designed, hardened, and thoroughly tested for use in Harsh Environments.
•CE Approved & UL / cUL Class I, Division 2 Approvals.
•FCC Conformity Class B.
•ATEX / IECEx Certified for Explosive Atmospheres.
II 3 G Ex nA IIC T3 Gc -40oC ≤Ta ≤+75oC
DEMKO 18 ATEX 2086XIECEx UL 18.0092X
•Carrier includes a voltage or current output at each output channel.
•Better than ±0.1% output accuracy.
•Wide ambient temperature operation from -40°C to +75°C.
•All I/O and power ports are transient protected.
•Wide-range isolated DC power input from 6-32V.
•LED indicators for module Bluetooth wireless technology link, module power,
and splitter output fault detection aides trouble-shooting.
•High 1500VAC safety Isolation between field input, each output, and power.
Individually isolated for common-mode voltage up to 250VAC, or 354V DC off
DC power ground, on a continuous basis (will withstand 1500VAC
HIPOT/dielectric strength test for one minute without breakdown). Complies
with test requirements of ANSI/ISA-82.01-1988 for voltage rating specified.
•Shock (25G) and Vibration Immunity (4G) - Conforms to: IEC 60068-2-6: 10-
500 Hz, 5G, 2 Hours/axis, for sinusoidal vibration; IEC 60068-2-64: 10-500 Hz,
5G-rms, 2 Hours/axis, for random vibration, and IEC 60068-2-27: 30G, 11ms
half-sine, 18 shocks at 6 orientations and 50G, 3ms half-sine, 18 shocks at 6
orientations, for mechanical shock.
•EMC (Electromagnetic Compatibility) –Min Immunity per BS EN 61000-6-1
(2007); CE marked, per EMC Directive 2014/30/EU. Electrostatic Discharge
Immunity (ESD), per IEC 61000-4-2; Radiated Field Immunity (RFI), per IEC
61000-4-3 and ETSI EN 301 489; Electrical Fast Transient Immunity (EFT), per
IEC 61000-4-4; Surge Immunity, per IEC 61000-4-5. Conducted RF Immunity
(CRFI), per IEC 61000-4-6.
•Emissions - This is a Class B Product with Emissions per BS EN 61000-6-3
(2007+A1:2011) and Spurious Emissions per ETSI EN 300 328. Enclosure Port,
per CISPR 16. Low Voltage AC Mains Port, per CISPR 16.
•Installation Category - Suitable for installation in a Pollution Degree 2
environment with an Installation Category (Over-voltage Category) II rating
per IEC 1010-1 (1990).