ARD2F
Intelligent motor Protector
Operating Manual
V1. 1
ACREL Co., Ltd

DeclarationAll rights reserved. Without the written permission of the Company, the contents of
any paragraph or section in this manual shall not be copied, copied or disseminated in
any form. Otherwise, all consequences shall be borne by the violator.
Our company reserves all legal rights.
Our company reserves the right to modify the product specifications described in this
manual without prior notice. Before placing an order, please consult your local agent
for new specifications of this produ ct

Catalog
1、Overview ............................................................................................... 1
2、Product Features .................................................................................... 1
3
、
Model Description ................................................................................ 1
4
、
M ain parameters .................................................................................... 3
5、Overall dimensions and installation ...................................................... 5
6、Protection function description ........................................................... 11
7、Function setting and description ......................................................... 26
8、Communication Settings and instructions .......................................... 45
9
、
Typical applications ............................................................................ 8 3
10
、
Features and Functions ..................................................................... 8 7
11
、
Examples of ordering ........................................................................ 8 9

1
1
1
1
1 Overview
Overview
Overview
Overview
The ARD 2F intelligent motor protector (hereinafter referred to as the protector) is suitable for
low-voltage motor circuits with rated voltage up to 660V and integrates protection, measurement,
control, communication, operation and maintenance.Its perfect protection function ensures the
safe operation of the motor, with logic programmable function, can meet a variety of control
methods.
The product adopts split structure, which is composed of main body, display unit, mutual
inductor and optional communication module, and can adapt to the installation of various cabinets.
Product Implementation standards:
—— GB 14048.4-2010 Low-voltage switchgear and control gear -- Part 4-1: Contactors and
motor starters -- Electromechanical contactors and motor starters (including motor protectors);
—— JB / T 10736-2007 Low voltage motor protector.
2
2
2
2 Product
Product
Product
Product Features
Features
Features
Features
■ Support fundamental and full-wave power parameter measurement (U, I,
P,
Q, S,
PF,
F,
EP,
EQ), voltage and current imbalance degree, voltage and current positive sequence, negative
sequence, zero sequence component, three-phase voltage phase Angle, residual current.
■ Protection functions include overload inverse time, overload definite time, grounding, starting
timeout, leakage, underload, locked-rotor, obstruction, short circuit, phase, overflow, imbalance
(current, voltage, power, less power, overvoltage, undervoltage, phase sequence, temperature,
external fault, tE time , running time alarm, fault alarm.
■ 9 channels programmable DI input, the default use of DC24V power supply, or external active
wet contact can be selected (see the selection table).
■ 5 programmable DO output, to meet the direct starting, star - triangle starting,
auto-transformer starting, and other starting modes, can be through the communication bus to
achieve the master station to the motor remote control "start/stop".
■ Optional anti-shaking function: support immediate restart of shaking power and restart of
voltage loss.
■ MODBUS_RTU and PROFIBUS DPV1 communication modules are available for selection.2
MODBUS_RTU communication channels or MODBUS _RTU + PROFIBUS DPV1
communication modules can be chosen.
■ Optional 1 channels DC 4-20MA analog output interface, connected with DCS system, can
realize the monitoring of field equipment.
■ With fault record, start record, stop record, DI displacement record, restart record and other
records of various events, you can view a number of motor operation and maintenance
information.
■ The display interface supports Chinese/English LIQUID crystal display
3
3
3
3 Model
Model
Model
Model Description
Description
Description
Description

2
ARD 2 F
/ +
Display module (Table 3 )
Additional functions (Table 2 )
Current Specification (Table 1 )
Split
D esign serial number
Enterprise code
The corresponding relation between ARD 2F current specification and the rated current and power
of the applicable motor is shown in Table 1 :
Table 1
Protector current
specification (A)
Ratio
setting
Primary side coil
number of transformer
Applicable scope
of motor (kW)
Suitable for motor
Rated current range (A)
1
Support
5circle
0.12- 999 0.1- 5000
5
1circle
0.12- 999 0. 5 - 5000
1.6
Does
not
support
1circle
0.12-0.55 0.4-1.6
6.3
1circle
0.75-2.2 1.6-6.3
25
1circle
3-11 6.3-25
100
1circle
15-45 25-100
250
1circle
55-132 63-250
800
1circle
160-250 250-800
Additional features of ARD 2F are shown in Table 2 :
Table 2
Additional f unction Code Additional f unction Code
Starting control (including K
function)
Q Leakage protection L
Switching input K 4-20mA analog output M
Temperature protection T Anti - electric shock function SU
Alarm (Programmable output) J SOE event record SR
1 channel
communication
Modbus_RTU C
2 channels
communication
2路M odbus_RTU 2C
Profibus _DP CP Modbus+Profibus CCP
Voltage function (phase sequence,
power, power factor)
U t E time protection tE
Energy metering Ep
See Table 3 for the ARD 2F display module:
Table 3
Display module code
90L
LCD display , module size 98 × 60, opening 92 × 55 (unit : mm)
Remarks :
(1)、 Current measuring and 2 channels of relay output DO4(97 、98) 、DO5(95 、96 、94) are

3
standard for ARD2F.
(2)、 When equipped with starting control, the protector provides no more than 2 starting relay
for the sequence control of the closing/opening of two external contactors to realize different
starting ways of motor (such as
Y-
Δ
transformation starting, positive and negative rotation control,
and self-coupling reduced-voltage starting, etc.)
(3)、 The additional function SU and Q should be chosen together.Additional function SU is
including U(voltage function) and SR(SOE event record).
(4) 、 The current specifications of 100A and below shall be the same type of current transformer.
The transformer is equipped with a secondary line of about 1m. If you need special line length,
please contact the manufacturer.The 250A and 800A current specifications use two other types of
transformers with no secondary wires.See "External Dimensions and Installation" for the
dimensions of the transformer .
(5)、The standard display cable is a network cable with a length of 1.5m. 3 meters and 5 meters
are available for optional configuration.
You
can place an order and remark the corresponding
cable length.
(6)、 For customers who do not need display modules, a batch of optional several display
modules can be used as a programmer, or the configuration software provided by the manufacturer
can be used to configure parameters through computer software.
(7)、 The temperature measurement support sensor type is PTC or NTC. 。
(8)、 After selecting the leakage function (L), each protector shall be equipped with a leakage
transformer. Please refer to the "External Dimensions and Installation" section for the dimensions
of the leakage transformer.The leakage transformer is equipped with a secondary wire of
2m ± 10cm. If other lengths are needed, please contact the manufacturer.
4
4
4
4 M
M
M
M ain
ain
ain
ain parameters
parameters
parameters
parameters
4.1 Technical indicators
ARD 2F technical indicators are shown in Table 4 :
Table 4
Technical parameters Technical indicators
Protector auxiliary
power supply
AC85-265V/DC100-350V
Rated working voltage
of the motor
AC220V / 380V / 660V ,50Hz / 60Hz
Rated operating current
of the motor
1 (0.1A- 5000 A)
External current transformer
5 (0.1A- 5000 A)
1.6A(0.4A-1.6A)
6.3A (1.6A-6.3A )
25 (6.3A-25A )
100 (25A-100A )
250 (63A-250A )
800 (250A-800A )
Relay output contact
capacity
Impedance load AC250V 、10 A

4
Switching input
9 channels of passive dry contact (active DC110V , DC220V, AC220V
input can be optional)
C ommunication RS485 Modbus_RTU,Profobus_DP
E nvironment
Working temperature -10 º C ~55 º C
Storage temperature -25 º C ~70 º C
Relative humidity
≤ 95 % No condensation, no corrosive
gas
A ltitude ≤ 2000m
Pollution levels Class 3
Protection grade
Main body IP20, split display module IP54 (installed on the cabinet
panel)
Install ation category Level III
4.2 Functional configuration
The ARD 2F functional configuration is shown in Table 5
Table 5
Type
Function
Functional configuration
S tandard function Optional function
Protection
function
Fixed time overload √
Inverse time overload √
Starting timeout √
Phase loss √
V
oltage unbalance √
C urrent unbalance √
Locked-Rotor √
underload √
External fault √
B lock √
Temperature protection (PTC/NTC )√
R esidual current
grounding √
leakage √ (leakage )
Phase sequence √
Under voltage √
Over voltage √
Under powe r √
Over powe r √
tE Time protect √
Overflow protection √
Alarm of starting times √
Running time alarm √
Fault frequency alarm √
C ontrol
mode
Protection mode √
Direct start mode
√Two-step mode

5
Two-speed mode
Y-
△start mode
Voltage loss restart √
Communica
tion
1 channel Modbus-RTU communication √
2 channel Modbus-RTU communication √
1 channel Profibus-DP communication √
1 channel Modbus-RTU+1 channel
Profibus-DP
√
Switching
input
9 channel DI (programmable) √
Relay
output
2 channel DO (programmable) √
5 channel DO (programmable) √
Analog
output
1 channel DC4-20mA √
E vent
record
Start record, stop record, DI
displacement record, restart record,
(support communication transmission
and U disk export)
√
Display unit
Liquid
crystal
display
(LCD)
Black and white dot
matrix LCD display
√
5
5
5
5 Overall
Overall
Overall
Overall dimensions
dimensions
dimensions
dimensions and
and
and
and installation
installation
installation
installation
5.1 The product composition of ARD 2F is shown in Figure 1, Figure 2
FIG. 1 Composition of products with 100A and below specifications

6
FIG. 2 Composition of 250A and 800A
5 . 2 Panel size and opening (Unit :mm )
The shape and opening size of the black and white liquid crystal display unit are shown in Figure 4:
Front view Side view Back view
Hole size
Fig .3 T he shape and hole size of 90L display unit
5 . 3 Size of main body module (unit: mm)
The ARD 2F main body is installed with 35mm guide rail, and its external dimensions are shown
in Figure 4 :

7
Front view Side view
Fig .4 ARD 2F main body dimensions
5 . 4 The external dimensions of current transformers of 100A and the following specifications are
shown in FIG. 5 (unit: mm) : :
5.4.1 The current transformer with the current specification of the protector is 100A, with the
standard secondary connection line length of 1m ± 10cm. If other lengths are needed, please contact
the manufacturer, for example, 3m and 5m lines are optional.The secondary lines of yellow, blue,
red and black correspond to the correlation of current A, B, C and the common end of the
transformer.
A
protector is equipped with a set of transformer.
F ig . 5 External dimensions of current transformers with specifications below 100A
5.4 .2 T he external dimensions of the 250A current transformer are shown in FIG. 6 (unit: mm) :
The current specification of the protector is the current transformer matched at 250A. There is no
secondary connection wire. One protector is equipped with three transformers.